Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

56

6SE6400-5BB00-0BP0

P0340[3]

Calculation of motor parameters

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: MOTOR

Active: first confirm

QuickComm.: No

Max: 4

Calculates various motor parameters (see table below). This parameter is required during commissioning to
optimize inverter performance.

Possible Settings:

0 No

calculation

1 Complete

parameterization

2

Calculation of equivalent circuit data

3

Calculation of V/f and vector control data

4

Calculation of controller settings only

Index:

P0340[0] : 1st. Drive data set (DDS)
P0340[1] : 2nd. Drive data set (DDS)
P0340[2] : 3rd. Drive data set (DDS)

Note:

P0340 = 0:
No calculation

P0340 = 1:
The motor weight/moment of inertia (P0344, P0341) are determined starting from the rating plate
parameters (P0300 - P0335), the motor equivalent circuit diagram parameters (ESB, P0350 - P0369). The
V/f control/vector control parameters and reference quantities are then pre-assigned (includes all of the
calculations from P0340 = 2,3,4).

P0340 = 2:
The motor equivalent circuit diagram parameters (ESB, P0350 - P0369) are calculated starting from the
rating plate parameters (without any other pre-assignments made).

P0340 = 3:
The V/f control/vector control parameters are determined (includes all calculations from P0340 = 4) starting
from the motor equivalent circuit diagram parameters (ESB, P0350 - P0369) and motor weight/moment of
inertia, moment of inertia ratio (P0344, P0341, P0342).

P0340 = 4:
The vector control parameters are pre-assigned starting from the motor equivalent circuit diagram
parameters (ESB, P0350 - P0369) and motor weight/moment of inertia, moment of inertia ratio (P0344,
P0341, P0342).

Level

2