Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

230

6SE6400-5BB00-0BP0

P2235[3]

BI: Enable PID-MOP (UP-cmd)

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

19:13

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source of UP command.

Index:

P2235[0] : 1st. Command data set (CDS)
P2235[1] : 2nd. Command data set (CDS)
P2235[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
19.D = Keypad UP button

Dependency:

To change setpoint:
1. Use UP / DOWN key on BOP or
2. Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)

P2236[3]

BI: Enable PID-MOP (DOWN-cmd)

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

19:14

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source of DOWN command.

Index:

P2236[0] : 1st. Command data set (CDS)
P2236[1] : 2nd. Command data set (CDS)
P2236[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.E = Keypad DOWN button

Dependency:

To change setpoint:
1. Use UP / DOWN key on BOP or
2. Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)

P2240[3] Setpoint

of

PID-MOP

Min: -200.00

CStat:

CUT

Datatype: Float Unit:

%

Def:

10.00

P-Group: TECH

Active: Immediately

QuickComm.: No

Max: 200.00

Setpoint of the motor potentiometer.

Allows user to set a digital PID setpoint in [%].

Index:

P2240[0] : 1st. Drive data set (DDS)
P2240[1] : 2nd. Drive data set (DDS)
P2240[2] : 3rd. Drive data set (DDS)

Note:

P2240 = 100 % corresponds to 4000 hex

Level

3

Level

3

Level

2