Siemens 440 User Manual
Page 101

Issue 01/06
Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
101
The actual active drive data set (DDS) is displayed in parameter r0051[1].
r0055
Bit05
r0055
Bit04
1. DDS
0
0
2. DDS
0
1
3. DDS
1
0
3. DDS
1
1
r0051 [0]
0
1
2
2
r0051 [1]
0
1
2
2
selected
DDS
active
DDS
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
Example:
a) Commissioning procedure with one motor:
-
Apply commissioning to DDS1
-
Connect P0820 (P0821 if necessary) with DDS source (i.e. via DIN 4: P0704[0] = 99, P0820 = 722.3)
-
Copy DDS1 to DDS2 (P0819[0] = 0, P0819[1] = 1, P0819[2] = 2)
-
Adapt DDS2 parameters (e.g. Ramp-up time P1120[1] and Ramp-down time P1121[1])
DIN
ADC
P0820 = 722.3
SUM
Setpoint
Sequence control
DIN4
AFM
RFG
Motor
control
0
1
P1120
P1121
[0]
DDS1
[1]
DDS2
[2]
DDS3
M
M
odul
at
or
b) Commissioning procedure with two motors (Motor 1, Motor 2):
-
Commission Motor 1; Adapt all other DDS1 parameters (as required)
-
Connect P0820 (P0821 if necessary) with DDS source (i.e. via DIN 4: P0704[0] = 99, P0820 = 722.3)
-
Switch-over to DDS2 (check it via r0051)
-
Commission Motor 2; Adapt all other DDS2 parameters (as required)
MM4
M1
K1
M2
K2
Motor 1
Motor 2
Note:
P0821 is also relevant for drive data set (DDS) selection.