29 control mode – Siemens 440 User Manual
Page 153
Issue 01/06
Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
153
3.29 Control
mode
P1300[3] Control
mode
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
0
P-Group: CONTROL
Active: first confirm
QuickComm.: Yes Max: 23
Controls relationship between speed of motor and voltage supplied by inverter as illustrated in the diagram
below.
V
n
0
f
n
V
f
V
P1325
f1
P1320
f
max
P1082
V
max
r0071
V
n
P0304
P1323
P1321
P1300 = 0
f0
0 Hz
f2
P1322
f3
P1324
f
n
P0310
f
P1300 = 3
P1310
P1300 = 2
Possible Settings:
0
V/f with linear characteristic
1 V/f
with
FCC
2
V/f with parabolic characteristic
3
V/f with programmable characteristic
4 Reserved
5
V/f for textile applications
6
V/f with FCC for textile applications
19 V/f control with independent voltage setpoint
20 Sensorless vector control
21 Vector control with sensor
22 Sensorless vector torque-control
23 Vector torque-control with sensor
Index:
P1300[0] : 1st. Drive data set (DDS)
P1300[1] : 2nd. Drive data set (DDS)
P1300[2] : 3rd. Drive data set (DDS)
Dependency:
See parameter P0205, P0500
Caution:
When commissioning Vector Control with encoder-feedback (VC), the drive should be configured for V/f
mode (see P1300) first. Run the drive and compare r0061 with r0021 that should agree in
- sign
and
-
magnitude (with a deviation of only a few percent).
Only if both criteria are fullfilled, change P1300 and select VC (P1300 = 21 or 23).
P0400 = 1 (single channel encoder) will only allow operation in one direction. If operation in both directions
is required, connect an encoder with 2 channels (A and B) and select setting 2. See the Operating
Instructions of the encoder module for more information.
Note:
P1300 = 1 : V/f with FCC (flux current control)
-
Maintains motor flux current for improved efficiency.
-
If FCC is chosen, linear V/f is active at low frequencies.
P1300 = 2 : V/f with a quadratic characteristic
-
Suitable for centrifugal fans / pumps
P1300 = 3 : V/f with a programmable characteristic
-
User defined characteristic (see P1320)
-
For synchronous motors (e.g. SIEMOSYN motors)
P1300 = 5,6 : V/f for textil applications
-
Slip compensation disabled.
-
Imax controller modifies the output voltage only.
-
Imax controller does not influence the output frequency.
Level
2