Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

58

6SE6400-5BB00-0BP0

P0341[3]

Motor inertia [kg*m^2]

Min: 0.00010

CStat:

CUT

Datatype: Float Unit:

-

Def:

0.00180

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 1000.00000

Sets no-load inertia of motor.

Together with P0342 (inertia ratio total/motor) and P1496 (scaling factor acceleration), this value produces
the acceleration torque (r1517), which can be added to any additional torque produced from a BICO source
(P1511), and incorporated in the torque control function.

Index:

P0341[0] : 1st. Drive data set (DDS)
P0341[1] : 2nd. Drive data set (DDS)
P0341[2] : 3rd. Drive data set (DDS)

Note:

The result of P0341 * P0342 is included in the speed controller calculation. P0341 * P0342 (inertia ratio
total/motor) = total motor inertia

P1496 (scaling factor acceleration) = 100 % activates acceleration pre-control for the speed controller and
calculates the torque from P0341 (motor inertia) and P0342 (inertia ratio total/motor).

P0342[3]

Total/motor inertia ratio

Min: 1.000

CStat:

CUT

Datatype: Float Unit:

-

Def:

1.000

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 400.000

Specifies ratio between total inertia (load + motor) and motor inertia.

Index:

P0342[0] : 1st. Drive data set (DDS)
P0342[1] : 2nd. Drive data set (DDS)
P0342[2] : 3rd. Drive data set (DDS)

P0344[3] Motor

weight

Min: 1.0

CStat:

CUT

Datatype: Float Unit:

kg

Def:

9.4

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 6500.0

Specifies motor weight [kg].

Index:

P0344[0] : 1st. Drive data set (DDS)
P0344[1] : 2nd. Drive data set (DDS)
P0344[2] : 3rd. Drive data set (DDS)

Note:

-

This value is used in the motor thermal model.

-

It is normally calculated automatically from P0340 (motor parameters) but can also be entered
manually.

-

Default value is depending on inverter type and its rating data.

r0345[3]

Motor start-up time

Min: -

Datatype: Float Unit:

s

Def:

-

P-Group: MOTOR

Max: -

Displays motor start-up time. This time corresponds to the standardized motor inertia.

The start-up time is the time taken to reach rated motor speed from standstill at acceleration with rated
motor torque (r0333).

Index:

r0345[0] : 1st. Drive data set (DDS)
r0345[1] : 2nd. Drive data set (DDS)
r0345[2] : 3rd. Drive data set (DDS)

P0346[3] Magnetization

time

Min: 0.000

CStat:

CUT

Datatype: Float Unit:

s

Def:

1.000

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 20.000

Sets magnetization time [s], i.e. waiting time between pulse enable and start of ramp-up. Motor
magnetization builds up during this time.

Magnetization time is normally calculated automatically from the motor data and corresponds to the rotor
time constant (r0384).

Index:

P0346[0] : 1st. Drive data set (DDS)
P0346[1] : 2nd. Drive data set (DDS)
P0346[2] : 3rd. Drive data set (DDS)

Note:

-

If boost settings are higher than 100 %, magnetization time may be reduced.

-

Default value is depending on inverter type and its rating data.

-

An excessive reduction of this time can result in insufficient motor magnetization.

Level

3

Level

3

Level

3

Level

3

Level

3