beautypg.com

Siemens 440 User Manual

Page 194

background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

194

6SE6400-5BB00-0BP0

P2002[3] Reference

current

Min: 0.10

CStat:

CT

Datatype: Float Unit:

A

Def:

0.10

P-Group: COMM

Active: first confirm

QuickComm.: No

Max: 10000.00

Full-scale output current used over serial link (corresponds to 4000H).

Index:

P2002[0] : 1st. Drive data set (DDS)
P2002[1] : 2nd. Drive data set (DDS)
P2002[2] : 3rd. Drive data set (DDS)

Example:

If a BICO connection is made between two parameters, the "unit" of the parameters (standardized (Hex) or
physical (i.e. A) values) may differ. MICROMASTER implicitly makes an automatic conversion to the target
value.

P2016

[0]
[1]
[2]
[3]

r0027

x[A]

y[Hex]

]

Hex

[

4000

P2002[A]

r0027[A]

y[Hex]

=

USS-PZD

BOP link

P2003[3] Reference

torque

Min: 0.10

CStat:

CT

Datatype: Float Unit:

Nm

Def:

0.12

P-Group: COMM

Active: first confirm

QuickComm.: No

Max: 99999.00

Full-scale reference torque used over the serial link (corresponds to 4000H).

Index:

P2003[0] : 1st. Drive data set (DDS)
P2003[1] : 2nd. Drive data set (DDS)
P2003[2] : 3rd. Drive data set (DDS)

Example:

If a BICO connection is made between two parameters or alternatively using P1500, the "unit" of the
parameters (standardized (Hex) or physical (i.e. Nm) values) may differ. MICROMASTER implicitly makes
an automatic conversion to the target value.

P2051

[0]

CB-PZD

COM link

[1]
[2]
[3]

r0080

x[Nm]

y[Hex]

]

Hex

[

4000

P2003[Nm]

r0080[Nm]

y[Hex]

=

P2004[3] Reference

power

Min: 0

CStat:

CT

Datatype: Float Unit:

-

Def:

P-Group: COMM

Active: first confirm

QuickComm.: No

Max: 0

Full-scale reference power used over the serial link (corresponds to 4000H).

P2003

P2000

M

f

2

2

1

r2004

π

=

π

=

Index:

P2004[0] : 1st. Drive data set (DDS)
P2004[1] : 2nd. Drive data set (DDS)
P2004[2] : 3rd. Drive data set (DDS)

Example:

If a BICO connection is made between two parameters, the "unit" of the parameters (standardized (Hex) or
physical (i.e. kW / hp) values) may differ. MICROMASTER implicitly makes an automatic conversion to the
target value.

P2019

[0]

USS

COM link

[1]
[2]
[3]

r0032

x[kW]

y[Hex]

]

Hex

[

4000

r2004

r0032

y[Hex]

=

or

x[hp]

depending on P0100

Level

3

Level

3

Level

3