Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
66
6SE6400-5BB00-0BP0
r0384[3]
Rotor time constant
Min: -
Datatype: Float Unit:
ms
Def:
-
P-Group: MOTOR
Max: -
Displays calculated rotor time constant [ms].
Index:
r0384[0] : 1st. Drive data set (DDS)
r0384[1] : 2nd. Drive data set (DDS)
r0384[2] : 3rd. Drive data set (DDS)
r0386[3]
Total leakage time constant
Min: -
Datatype: Float Unit:
ms
Def:
-
P-Group: MOTOR
Max: -
Displays total leakage time constant of motor.
Index:
r0386[0] : 1st. Drive data set (DDS)
r0386[1] : 2nd. Drive data set (DDS)
r0386[2] : 3rd. Drive data set (DDS)
r0394
CO: Stator resistance IGBT [%]
Min: -
Datatype: Float Unit:
%
Def:
-
P-Group: MOTOR
Max: -
Displays stator resistance calculated in [%] from IGBT ON voltage and current amplitude.
Note:
%
100
<=>
0305
P
3
0304
P
I
3
V
N
N
⋅
=
⋅
=
Z
N
=
ph
V
ph
I
Rated motor impedance:
r0395
CO: Total stator resistance [%]
Min: -
Datatype: Float Unit:
%
Def:
-
P-Group: MOTOR
Max: -
Displays the actual stator resistance (combined stator/cable resistance) of the motor as a [%] as a function
of the actual stator winding temperature.
Note:
Actual stator winding temperature, refer to r0632
%
100
<=>
0305
P
3
0304
P
I
3
V
N
N
⋅
=
⋅
=
Z
N
=
ph
V
ph
I
Rated motor impedance:
r0396
CO: Act. rotor resistance
Min: -
Datatype: Float Unit:
%
Def:
-
P-Group: MOTOR
Max: -
Displays the actual rotor resistance of the motor equivalent circuit diagram (phase value) as a [%] as a
function of the actual rotor winding temperature.
Note:
-
Actual rotor winding temperature, refer to r0633
-
Values greater than 25 % tend to produce excessive motor slip. Check rated motor speed [rpm] value
(P0311).
%