Siemens 440 User Manual
Page 59
Issue 01/06
Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
59
P0347[3] Demagnetization
time
Min: 0.000
CStat:
CUT
Datatype: Float Unit:
s
Def:
1.000
P-Group: MOTOR
Active: Immediately
QuickComm.: No
Max: 20.000
Defines the de-magnetization time for the connected induction motor.
The de-magnetization time is the time that must expire between powering-down the drive (OFF2 or a drive
inverter fault/error) and powering-up again. The drive inverter is prevented from being powered-up again
within this time interval. The flux in the induction motor is reduced to a low value during this de-
magnetization time.
OFF1
ON
t
t
f
t
OFF2
active
P0347
inactive
OFF2
Motor coasts down
Index:
P0347[0] : 1st. Drive data set (DDS)
P0347[1] : 2nd. Drive data set (DDS)
P0347[2] : 3rd. Drive data set (DDS)
Note:
-
The de-magnetization time is approximately 250% of the rotor time constant (r0384) in seconds.
-
The pre-assignment (default value) depends on the drive inverter type and its rated/nominal values.
-
It is not active after a normal ramp-down - i.e. after OFF1 or OFF3.
-
If this time is excessively shortened, then the drive inverter will be tripped (shut down) due to an
overcurrent condition.
-
If a synchronous motor is connected, the de-magnetization time should be set to 0.
P0350[3]
Stator resistance (line-to-line)
Min: 0.00001
CStat:
CUT
Datatype: Float Unit:
Ohm
Def:
4.00000
P-Group: MOTOR
Active: Immediately
QuickComm.: No
Max: 2000.00000
Stator resistance value in [Ohms] for connected motor (from line-to-line). The parameter value includes the
cable resistance.
)
R
R
(
2
0350
P
S
Cable
+
⋅
=
There are three ways to determine the value for this parameter:
1. Calculate
using
-
P0340 = 1 (data entered from rating plate) or
-
P0010 = 1, P3900 = 1,2 or 3 (end of quick commissioning).
2. Measure using P1910 = 1 (motor data identification - value for stator resistance is overwritten).
3. Measure manually using an Ohmmeter.
Index:
P0350[0] : 1st. Drive data set (DDS)
P0350[1] : 2nd. Drive data set (DDS)
P0350[2] : 3rd. Drive data set (DDS)
Note:
-
Since measured line-to-line, this value may appear to be higher (up to 2 times higher) than expected.
-
The value entered in P0350 (stator resistance) is the one obtained by the method last used.
-
Default value is depending on inverter type and its rating data.
Level
3
Level
2