beautypg.com

Siemens 440 User Manual

Page 59

background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

59

P0347[3] Demagnetization

time

Min: 0.000

CStat:

CUT

Datatype: Float Unit:

s

Def:

1.000

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 20.000

Defines the de-magnetization time for the connected induction motor.

The de-magnetization time is the time that must expire between powering-down the drive (OFF2 or a drive
inverter fault/error) and powering-up again. The drive inverter is prevented from being powered-up again
within this time interval. The flux in the induction motor is reduced to a low value during this de-
magnetization time.

OFF1

ON

t

t

f

t

OFF2

active

P0347

inactive

OFF2

Motor coasts down

Index:

P0347[0] : 1st. Drive data set (DDS)
P0347[1] : 2nd. Drive data set (DDS)
P0347[2] : 3rd. Drive data set (DDS)

Note:

-

The de-magnetization time is approximately 250% of the rotor time constant (r0384) in seconds.

-

The pre-assignment (default value) depends on the drive inverter type and its rated/nominal values.

-

It is not active after a normal ramp-down - i.e. after OFF1 or OFF3.

-

If this time is excessively shortened, then the drive inverter will be tripped (shut down) due to an
overcurrent condition.

-

If a synchronous motor is connected, the de-magnetization time should be set to 0.

P0350[3]

Stator resistance (line-to-line)

Min: 0.00001

CStat:

CUT

Datatype: Float Unit:

Ohm

Def:

4.00000

P-Group: MOTOR

Active: Immediately

QuickComm.: No

Max: 2000.00000

Stator resistance value in [Ohms] for connected motor (from line-to-line). The parameter value includes the
cable resistance.

)

R

R

(

2

0350

P

S

Cable

+

=


There are three ways to determine the value for this parameter:
1. Calculate

using

-

P0340 = 1 (data entered from rating plate) or

-

P0010 = 1, P3900 = 1,2 or 3 (end of quick commissioning).

2. Measure using P1910 = 1 (motor data identification - value for stator resistance is overwritten).
3. Measure manually using an Ohmmeter.

Index:

P0350[0] : 1st. Drive data set (DDS)
P0350[1] : 2nd. Drive data set (DDS)
P0350[2] : 3rd. Drive data set (DDS)

Note:

-

Since measured line-to-line, this value may appear to be higher (up to 2 times higher) than expected.

-

The value entered in P0350 (stator resistance) is the one obtained by the method last used.

-

Default value is depending on inverter type and its rating data.

Level

3

Level

2