Siemens 440 User Manual
Page 243
Issue 01/06
Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
243
P2810[2]
BI: AND 1
Min: 0:0
CStat:
CUT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: TECH
Active: first confirm
QuickComm.: No
Max: 4000:0
P2810[0], P2810[1] define inputs of AND 1 element, output is P2811.
P2800 P2801[0]
A
B
C
&
P2810
r2811
A
B
C
0
0
0
0
1
0
1
0
0
1
1
1
Index0
Index1
Index:
P2810[0] : Binector input 0 (BI 0)
P2810[1] : Binector input 1 (BI 1)
Dependency:
P2801[0] is active level for the AND element.
r2811
BO: AND 1
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: TECH
Max: -
Output of AND 1 element. Displays and logic of bits defined in P2810[0], P2810[1].
Dependency:
P2801[0] is active level for the AND element.
P2812[2]
BI: AND 2
Min: 0:0
CStat:
CUT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: TECH
Active: first confirm
QuickComm.: No
Max: 4000:0
P2812[0], 2812[1] define inputs of AND 2 element, output is P2813.
Index:
P2812[0] : Binector input 0 (BI 0)
P2812[1] : Binector input 1 (BI 1)
Dependency:
P2801[1] is active level for the AND element.
r2813
BO: AND 2
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: TECH
Max: -
Output of AND 2 element. Displays and logic of bits defined in P2812[0], P2812[1].
Dependency:
P2801[1] is active level for the AND element.
P2814[2]
BI: AND 3
Min: 0:0
CStat:
CUT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: TECH
Active: first confirm
QuickComm.: No
Max: 4000:0
P2814[0], P2814[1] define inputs of AND 3 element, output is P2815.
Index:
P2814[0] : Binector input 0 (BI 0)
P2814[1] : Binector input 1 (BI 1)
Dependency:
P2801[2] is active level for the AND element.
r2815
BO: AND 3
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: TECH
Max: -
Output of AND 3 element. Displays and logic of bits defined in P2814[0], P2814[1].
Dependency:
P2801[2] is active level for the AND element.
Level
3
Level
3
Level
3
Level
3
Level
3
Level
3