Siemens 440 User Manual
Page 108
Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
108
6SE6400-5BB00-0BP0
P0952
Total number of faults
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
0
P-Group: ALARMS
Active: first confirm
QuickComm.: No
Max: 8
Displays number of faults stored in r0947 (last fault code).
Dependency:
Setting 0 resets fault history. (changing to 0 also resets parameter r0948 - fault time).
r0964[5]
Firmware version data
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: COMM
Max: -
Firmware version data.
Index:
r0964[0] : Company (Siemens = 42)
r0964[1] : Product type
r0964[2] : Firmware version
r0964[3] : Firmware date (year)
r0964[4] : Firmware date (day/month)
Example:
reserved
r0964[0]
42
SIEMENS
1001 MICROMASTER 420
1002 MICROMASTER 440
1003 MICRO- / COMBIMASTER 411
1004 MICROMASTER 410
1005
1006
r0964[1]
MICROMASTER 440 PX
No.
Value Meaning
1007 MICROMASTER 430
r0964[2]
105
r0964[3]
2001
r0964[4]
2710
27.10.2001
Firmware V1.05
r0965 Profibus
profile
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: COMM
Max: -
Identification of profile number and version for PROFIDrive.
r0967 Control
word
1
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: COMM
Max: -
Displays control word 1.
Bitfields:
Bit00 ON/OFF1 0 NO 1 YES
Bit01 OFF2: Electrical stop 0 YES 1 NO
Bit02 OFF3: Fast stop 0 YES 1 NO
Bit03 Pulses enabled 0 NO 1 YES
Bit04 RFG enable 0 NO 1 YES
Bit05 RFG start 0 NO 1 YES
Bit06 Setpoint enable 0 NO 1 YES
Bit07 Fault acknowledge 0 NO 1 YES
Bit08 JOG right 0 NO 1 YES
Bit09 JOG left 0 NO 1 YES
Bit10 Control from PLC 0 NO 1 YES
Bit11 Reverse (setpoint inversion) 0 NO 1 YES
Bit13 Motor potentiometer MOP up 0 NO 1 YES
Bit14 Motor potentiometer MOP down 0 NO 1 YES
Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES
Level
3
Level
3
Level
3
Level
3