18 motorized potentiometer (mop) – Siemens 440 User Manual
Page 120
Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
120
6SE6400-5BB00-0BP0
3.18
Motorized potentiometer (MOP)
P1031[3]
Setpoint memory of the MOP
Min: 0
CStat:
CUT
Datatype: U16 Unit:
-
Def:
0
P-Group: SETPOINT
Active: Immediately
QuickComm.: No
Max: 1
Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down.
Possible Settings:
0
MOP setpoint will not be stored
1
MOP setpoint will be stored (P1040 is updated)
Index:
P1031[0] : 1st. Drive data set (DDS)
P1031[1] : 2nd. Drive data set (DDS)
P1031[2] : 3rd. Drive data set (DDS)
Note:
On next ON command, motor potentiometer setpoint will be the saved value in parameter P1040 (setpoint
of the MOP).
P1032
Inhibit negative MOP setpoints
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
1
P-Group: SETPOINT
Active: first confirm
QuickComm.: No
Max: 1
This parameter suppresses negative setpoints of the MOP output r1050.
Possible Settings:
0
Neg. MOP setpoint is allowed
1
Neg. MOP setpoint inhibited
Note:
The reversing functions (e.g. BOP-Reverse button if P0700 = 1) are not affected by the settings of P1032.
Use P1110 to fully prevent change of direction in setpoint channel.
P1035[3]
BI: Enable MOP (UP-command)
Min: 0:0
CStat:
CT
Datatype: U32 Unit:
-
Def:
19:13
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 4000:0
Defines source for motor potentiometer setpoint increase frequency.
Index:
P1035[0] : 1st. Command data set (CDS)
P1035[1] : 2nd. Command data set (CDS)
P1035[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.D = MOP up via BOP
P1036[3]
BI: Enable MOP (DOWN-command)
Min: 0:0
CStat:
CT
Datatype: U32 Unit:
-
Def:
19:14
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 4000:0
Defines source for motor potentiometer setpoint decrease frequency.
Index:
P1036[0] : 1st. Command data set (CDS)
P1036[1] : 2nd. Command data set (CDS)
P1036[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.E = MOP down via BOP
Level
2
Level
2
Level
3
Level
3