3 parameter description, 1 common parameters – Siemens 440 User Manual
Page 25
Issue 01/06
Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
25
3 Parameter
Description
Note
Level 4 Parameters are not visible with BOP or AOP.
3.1 Common
parameters
r0000 Drive
display
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: ALWAYS
Max: -
Displays the user selected output as defined in P0005.
Note:
Pressing the "Fn" button for 2 seconds allows the user to view the values of DC link voltage, output
frequency, output voltage, output current, and chosen r0000 setting (defined in P0005).
r0002 Drive
state
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: COMMANDS
Max: -
Displays actual drive state.
Possible Settings:
0 Commissioning
mode
(P0010
!=
0)
1 Drive
ready
2
Drive fault active
3
Drive starting (DC-link precharging)
4 Drive
running
5
Stopping (ramping down)
Dependency:
State 3 visible only while precharging DC link, and when externally powered communications board is fitted.
P0003 User
access
level
Min: 0
CStat:
CUT
Datatype: U16 Unit:
-
Def:
1
P-Group: ALWAYS
Active: first confirm
QuickComm.: No
Max: 4
Defines user access level to parameter sets. The default setting (standard) is sufficient for most simple
applications.
Possible Settings:
0
User defined parameter list - see P0013 for details on use
1
Standard: Allows access into most frequently used parameters.
2
Extended: Allows extended access e.g. to inverter I/O functions.
3
Expert: For expert use only.
4
Service: Only for use by authorized service personal - password protected.
P0004 Parameter
filter
Min: 0
CStat:
CUT
Datatype: U16 Unit:
-
Def:
0
P-Group: ALWAYS
Active: first confirm
QuickComm.: No
Max: 22
Filters available parameters according to functionality to enable a more focussed approach to
commissioning.
Possible Settings:
0 All
parameters
2 Inverter
3 Motor
4 Speed
sensor
5
Technol. application / units
7
Commands, binary I/O
8
ADC and DAC
10 Setpoint channel / RFG
12 Drive
features
13 Motor
control
20 Communication
21 Alarms / warnings / monitoring
22 Technology controller (e.g. PID)
Example:
P0004 = 22 specifies that only PID parameters will be visible.
Level
1
Level
2
Level
1
Level
1