Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
38
6SE6400-5BB00-0BP0
r0064
CO: Dev. frequency controller
Min: -
Datatype: Float Unit:
Hz
Def:
-
P-Group: CONTROL
Max: -
Displays actual deviation of speed controller.
This value is calculated from the frequency setpoint (r0062) and the actual frequency (r0063).
Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value
zero.
r0065
CO: Slip frequency
Min: -
Datatype: Float Unit:
%
Def:
-
P-Group: CONTROL
Max: -
Displays slip frequency of motor in [%] relative to the rated motor frequency (P0310).
Details:
For V/f control, see also P1335 (slip compensation).
r0066
CO: Act. output frequency
Min: -
Datatype: Float Unit:
Hz
Def:
-
P-Group: CONTROL
Max: -
Displays actual output frequency.
Note:
The output frequency is limited by the values entered in P1080 (min. frequency) and P1082 (max.
frequency).
r0067
CO: Act. output current limit
Min: -
Datatype: Float Unit:
A
Def:
-
P-Group: CONTROL
Max: -
Displays valid maximum output current of inverter.
Parameter r0067 is influenced/determined by the following factors:
-
Rated motor current P0305
-
Motor overload factor P0640
-
Motor protection in dependency of P0610
-
r0067 is less than or equal to maximum inverter current r0209
-
Inverter protection in dependency of P0290
Motor
Inverter
Motor protection
P0640
r0067
P0305
Inverter protection
r0209
Min
Note:
A reduction of r0067 may indicate an inverter overload or a motor overload.
r0068 CO:
Output
current
Min: -
Datatype: Float Unit:
A
Def:
-
P-Group: CONTROL
Max: -
Displays unfiltered [rms] value of motor current [A].
Note:
This is used for the process control (contrary to the smoothed output current r0027, that is used for display).
r0069[6]
CO: Act. phase currents
Min: -
Datatype: Float Unit:
A
Def:
-
P-Group: CONTROL
Max: -
Displays phase currents.
Index:
r0069[0] : U_phase
r0069[1] : V_phase
r0069[2] : W_phase
r0069[3] : Offset U_phase
r0069[4] : Offset V_phase
r0069[5] : Offset W_phase
Level
3
Level
3
Level
3
Level
3
Level
3
Level
4