2 alarm messages, A0501 current limit value, A0502 overvoltage limit value – Siemens 440 User Manual
Page 315: A0503 undervoltage limit value, A0504 inverter overtemperature, A0506 inverter load duty cycle
Issue 01/06
Faults and Alarms
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
315
5.2 Alarm
Messages
Alarm messages are stored in parameter r2110 under their code number (e.g. A0503
= 503) and can be read out from there.
A0501 Current limit value
Cause
-
the motor power rating does not correspond to the inverter power rating
-
motor cables are too long
- ground
fault
Diagnosis & Remedy
Please check the following:
-
does the motor power rating (P0307) match the inverter power rating (r0206) ?
-
are the limit values for the cable lengths maintained ?
-
does the motor cable or motor have a short-circuit or ground fault ?
-
do the motor parameters correspond to those of the motor being used ?
-
stator resistance value (P0350) correct ?
-
is the motor overloaded or is the rotor locked (cannot rotate) ?
-
ramp-up time P1120 too low ?
A0502 Overvoltage limit value
Cause
-
the overvoltage limit value has been reached (actual value of the DC link voltage r0026 greater than
r1242).
Diagnosis & Remedy
-
if this alarm is permanently displayed, check the inverter input voltage.
-
is the DC link voltage controller (Vdc_max controller) de-activated (refer to parameter P1240) ?
-
short ramp times and/or large flywheel masses (moment of inertia) ?
A0503 Undervoltage limit value
Cause
-
line supply has failed.
-
line voltage and therefore also the DC link voltage (r0026) below the defined limit value (refer to
parameter r0026).
Diagnosis & Remedy
-
check the line voltage.
A0504 Inverter
overtemperature
Cause
-
alarm threshold of the inverter heatsink temperature (P0614) was exceeded; this results in a reduction
of the pulse frequency and/or the output frequency (dependent on the parameterization in (P0610).
Diagnosis & Remedy
Please check the following:
-
is the ambient temperature within the permissible limits ?
-
are the load and load duty cycle within the permissible limits ?
A0505 Inverter
I2T
Cause
-
overload alarm limit P0294 is exceeded (refer to utilization r0036)
-
the pulse frequency and/or the output frequency is reduced as a function of the setting of parameter
P0290.
Diagnosis & Remedy
-
check whether the load duty cycle lies within the permissible limits.
A0506 Inverter load duty cycle
Cause
-
difference between the temperature at the heatsink and IGBT exceeds the alarm limit values.
Diagnosis & Remedy
-
please ensure that the load duty cycle and load surge lie within the permissible limits.