Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
204
6SE6400-5BB00-0BP0
P2040
CB telegram off time
Min: 0
CStat:
CT
Datatype: U16 Unit:
ms
Def:
20
P-Group: COMM
Active: Immediately
QuickComm.: No
Max: 65535
Defines time after which a fault will be generated (F0070) if no telegram is received via the link.
The telegramm off time defines the time, within which a valid telegram must be received. If no valid telegram
is received within that time, the inverter trips with F0070.
Dependency:
Setting 0 = watchdog disabled
P2041[5] CB
parameter
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
0
P-Group: COMM
Active: first confirm
QuickComm.: No
Max: 65535
Configures a communication board (CB).
Index:
P2041[0] : CB parameter 0
P2041[1] : CB parameter 1
P2041[2] : CB parameter 2
P2041[3] : CB parameter 3
P2041[4] : CB parameter 4
Details:
See relevant communication board manual for protocol definition and appropriate settings.
r2050[8]
CO: PZD from CB
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: COMM
Max: -
Displays PZD received from communication board (CB).
.
.
.
r2091
r2090
[0]
r2050
[1]
[2]
[3]
[7]
PKW
PZD
STW
HSW
PZD1
STW1
PZD2
HSW
PZD3
PZD4
STW2
P2041[0]
CB telegram
CB on COM link
PZD mapping to parameter r2050
Parameter ID value
Process data
Control word
Main setpoint
CB-Frame
PKW
PZD
CB-Frame
Process data
Parameter
Index:
r2050[0] : Received word 0
r2050[1] : Received word 1
r2050[2] : Received word 2
r2050[3] : Received word 3
r2050[4] : Received word 4
r2050[5] : Received word 5
r2050[6] : Received word 6
r2050[7] : Received word 7
Note:
The control words can be viewed as bit parameters r2090 and r2091.
Restrictions:
-
If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be
transferred in the 1st PZD-word.
-
If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the
2nd PZD-word,
-
When P2012 is greater than or equal to 4 the additional control word (2nd control word) must
transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).
Level
3
Level
3
Level
3