Siemens 440 User Manual
Page 116

Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
116
6SE6400-5BB00-0BP0
P1012[3]
Fixed frequency 12
Min: -650.00
CStat:
CUT
Datatype: Float Unit:
Hz
Def:
55.00
P-Group: SETPOINT
Active: Immediately
QuickComm.: No
Max: 650.00
Defines fixed frequency setpoint 12.
Index:
P1012[0] : 1st. Drive data set (DDS)
P1012[1] : 2nd. Drive data set (DDS)
P1012[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
P1013[3]
Fixed frequency 13
Min: -650.00
CStat:
CUT
Datatype: Float Unit:
Hz
Def:
60.00
P-Group: SETPOINT
Active: Immediately
QuickComm.: No
Max: 650.00
Defines fixed frequency setpoint 13.
Index:
P1013[0] : 1st. Drive data set (DDS)
P1013[1] : 2nd. Drive data set (DDS)
P1013[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
P1014[3]
Fixed frequency 14
Min: -650.00
CStat:
CUT
Datatype: Float Unit:
Hz
Def:
65.00
P-Group: SETPOINT
Active: Immediately
QuickComm.: No
Max: 650.00
Defines fixed frequency setpoint 14.
Index:
P1014[0] : 1st. Drive data set (DDS)
P1014[1] : 2nd. Drive data set (DDS)
P1014[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
P1015[3]
Fixed frequency 15
Min: -650.00
CStat:
CUT
Datatype: Float Unit:
Hz
Def:
65.00
P-Group: SETPOINT
Active: Immediately
QuickComm.: No
Max: 650.00
Defines fixed frequency setpoint 15.
Index:
P1015[0] : 1st. Drive data set (DDS)
P1015[1] : 2nd. Drive data set (DDS)
P1015[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1001 (fixed frequency 1).
P1016[3]
Fixed frequency mode - Bit 0
Min: 1
CStat:
CT
Datatype: U16 Unit:
-
Def:
1
P-Group: SETPOINT
Active: first confirm
QuickComm.: No
Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1016 defines the mode of selection
Bit 0.
Possible Settings:
1 Direct
selection
2
Direct selection + ON command
3
Binary coded selection + ON command
Index:
P1016[0] : 1st. Command data set (CDS)
P1016[1] : 2nd. Command data set (CDS)
P1016[2] : 3rd. Command data set (CDS)
Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.
Level
2
Level
2
Level
2
Level
2
Level
3