beautypg.com

22 flying restart – Siemens 440 User Manual

Page 136

background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

136

6SE6400-5BB00-0BP0

3.22 Flying

restart

P1200 Flying

start

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

0

P-Group: FUNC

Active: first confirm

QuickComm.: No

Max: 6

Starts inverter onto a spinning motor by rapidly changing the output frequency of the inverter until the actual
motor speed has been found. Then, the motor runs up to setpoint using the normal ramp time.

V out

I dc

I out

Vn

P1202

fout

t

(f

max

+ 2f

slip nom

)

'motor speed found'

'ramps to set point

with normal ramp'

as per V/f

characteristic

t

t

t

Possible Settings:

0

Flying start disabled

1

Flying start is always active, start in direction of setpoint

2

Flying start is active if power on, fault, OFF2, start in direction of setpoint

3

Flying start is active if fault, OFF2, start in direction of setpoint

4

Flying start is always active, only in direction of setpoint

5

Flying start is active if power on, fault, OFF2, only in direction of setpoint

6

Flying start is active if fault, OFF2, only in direction of setpoint

Note:

-

Useful for motors with high inertia loads.

-

Settings 1 to 3 search in both directions.

-

Settings 4 to 6 search only in direction of setpoint.

-

Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break)
or can be driven by the load. Otherwise, overcurrent trips will occur.

Level

2