r0052
CO/BO: Act. status word 1
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: COMMANDS
Max: -
Displays first active status word of inverter (bit format) and can be used to diagnose inverter status.
Bitfields:
Bit00 Drive ready 0 NO 1 YES
Bit01 Drive ready to run 0 NO 1 YES
Bit02 Drive running 0 NO 1 YES
Bit03 Drive fault active 0 NO 1 YES
Bit04 OFF2 active 0 YES 1 NO
Bit05 OFF3 active 0 YES 1 NO
Bit06 ON inhibit active 0 NO 1 YES
Bit07 Drive warning active 0 NO 1 YES
Bit08 Deviation setpoint / act. value 0 YES 1 NO
Bit09 PZD control 0 NO 1 YES
Bit10 Maximum frequency reached 0 NO 1 YES
Bit11 Warning: Motor current limit 0 YES 1 NO
Bit12 Motor holding brake active 0 NO 1 YES
Bit13 Motor overload 0 YES 1 NO
Bit14 Motor runs right 0 NO 1 YES
Bit15 Inverter overload 0 YES 1 NO
Dependency:
t
0
Power ON
t
r0052
Bit00
Drive ready
1
0
1
t
ON/OFF1
0
1
t
0
1
t
r0052
Bit01
Drive ready to run
0
1
t
Pulse enable
0
1
t
r0052
Bit02
Drive running
0
1
t
r0053
Bit09
0
1
Pre-charging active
Ramping finished
r0052 Bit00 - Bit02:
State-sequence diagram after Power On or ON/OFF1 respectively: ==> see below
r0052 Bit03 "Drive fault active":
Output of Bit3 (Fault) will be inverted on digital output (Low = Fault, High = No Fault).
r0052 Bit08 "Deviation setpoint / act. value" ==> see parameter P2164
r0052 Bit10 "f_act >= P1082 (f_max)" ==> see parameter P1082
r0052 Bit12 "Motor holding brake active" ==> see parameter P1215