Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
80
6SE6400-5BB00-0BP0
P0706[3]
Function of digital input 6
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
15
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 99
Selects function of digital input 6.
Possible Settings:
0
Digital input disabled
1 ON/OFF1
2
ON reverse /OFF1
3
OFF2 - coast to standstill
4
OFF3 - quick ramp-down
9 Fault
acknowledge
10 JOG
right
11 JOG
left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (Direct selection)
16 Fixed setpoint (Direct selection + ON)
25 DC brake enable
29 External
trip
33 Disable additional freq setpoint
99 Enable BICO parameterization
Index:
P0706[0] : 1st. Command data set (CDS)
P0706[1] : 2nd. Command data set (CDS)
P0706[2] : 3rd. Command data set (CDS)
Details:
See P0701 (function of digital input 1).
P0707[3]
Function of digital input 7
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
0
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 99
Selects function of digital input 7 (via analog input).
Possible Settings:
0
Digital input disabled
1 ON/OFF1
2
ON reverse /OFF1
3
OFF2 - coast to standstill
4
OFF3 - quick ramp-down
9 Fault
acknowledge
10 JOG
right
11 JOG
left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
25 DC brake enable
29 External
trip
33 Disable additional freq setpoint
99 Enable BICO parameterization
Index:
P0707[0] : 1st. Command data set (CDS)
P0707[1] : 2nd. Command data set (CDS)
P0707[2] : 3rd. Command data set (CDS)
Note:
Signals above 4 V are active, signals below 1,6 V are inactive.
Details:
See P0701 (function of digital input 1).
Level
2
Level
2