Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
208
6SE6400-5BB00-0BP0
P2104[3]
BI: 2. Faults acknowledgement
Min: 0:0
CStat:
CT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 4000:0
Selects second source of fault acknowledgement.
Index:
P2104[0] : 1st. Command data set (CDS)
P2104[1] : 2nd. Command data set (CDS)
P2104[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
P2106[3] BI:
External
fault
Min: 0:0
CStat:
CT
Datatype: U32 Unit:
-
Def:
1:0
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 4000:0
Selects source of external faults.
Index:
P2106[0] : 1st. Command data set (CDS)
P2106[1] : 2nd. Command data set (CDS)
P2106[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
r2110[4] Warning
number
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: ALARMS
Max: -
Displays warning information.
A maximum of 2 active warnings (indices 0 and 1) and 2 historical warnings (indices 2 and 3) may be
viewed.
Index:
r2110[0] : Recent Warnings --, warning 1
r2110[1] : Recent Warnings --, warning 2
r2110[2] : Recent Warnings -1, warning 3
r2110[3] : Recent Warnings -1, warning 4
Note:
-
Indices 0 and 1 are not stored.
-
The keypad will flash while a warning is active. The LEDs indicate the warning status in this case.
-
If an AOP is in use, the display will show number and text of the active warning.
P2111
Total number of warnings
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
0
P-Group: ALARMS
Active: first confirm
QuickComm.: No
Max: 4
Displays number of warning (up to 4) since last reset. Set to 0 to reset the warning history.
Level
3
Level
3
Level
2
Level
3