Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
125
3.20 Setpoint
channel
P1070[3]
CI: Main setpoint
Min: 0:0
CStat:
CT
Datatype: U32 Unit:
-
Def:
755:0
P-Group: SETPOINT
Active: first confirm
QuickComm.: No
Max: 4000:0
Defines source of main setpoint.
Index:
P1070[0] : 1st. Command data set (CDS)
P1070[1] : 2nd. Command data set (CDS)
P1070[2] : 3rd. Command data set (CDS)
Common Settings:
755 = Analog input 1 setpoint
1024 = Fixed frequency setpoint
1050 = Motor potentiometer (MOP) setpoint
P1071[3]
CI: Main setpoint scaling
Min: 0:0
CStat:
CT
Datatype: U32 Unit:
-
Def:
1:0
P-Group: SETPOINT
Active: first confirm
QuickComm.: No
Max: 4000:0
Defines source of the main setpoint scaling.
Index:
P1071[0] : 1st. Command data set (CDS)
P1071[1] : 2nd. Command data set (CDS)
P1071[2] : 3rd. Command data set (CDS)
Common Settings:
755 = Analog input 1 setpoint
1024 = Fixed frequency setpoint
1050 = Motor potentiometer (MOP) setpoint
P1074[3]
BI: Disable additional setpoint
Min: 0:0
CStat:
CUT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 4000:0
Disables additional setpoint
Index:
P1074[0] : 1st. Command data set (CDS)
P1074[1] : 2nd. Command data set (CDS)
P1074[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99))
P1075[3]
CI: Additional setpoint
Min: 0:0
CStat:
CT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: SETPOINT
Active: first confirm
QuickComm.: No
Max: 4000:0
Defines source of the additional setpoint (to be added to main setpoint).
Index:
P1075[0] : 1st. Command data set (CDS)
P1075[1] : 2nd. Command data set (CDS)
P1075[2] : 3rd. Command data set (CDS)
Common Settings:
755 = Analog input 1 setpoint
1024 = Fixed frequency setpoint
1050 = Motor potentiometer (MOP) setpoint