Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
140
6SE6400-5BB00-0BP0
0
−
−
−
−
−
1
−
−
2
+
−
−
−
3
+
+
+
+
4
+
+
−
−
−
5
+
−
+
+
6
+
+
+
+
+
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
restart
restart
restart
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
restart
Fault acknowl.
Fault acknowl.
restart
restart
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
restart
ON always active (permanent)
P1210
ON in no-voltage condition
Fault F0003 on
All other faults on
Brownout
Blackout
Brownout
Blackout
All faults on
Blackout
−
−
−
Restart
No faults on
Blackout
−
+
Fault acknowl.
restart
−
−
Fault acknowl.
Restart
Restart
Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or
can be driven by the load (P1200).
P1211
Number of restart attempts
Min: 0
CStat:
CUT
Datatype: U16 Unit:
-
Def:
3
P-Group: FUNC
Active: first confirm
QuickComm.: No
Max: 10
Specifies number of times inverter will attempt to restart if automatic restart P1210 is activated.
Level
3