beautypg.com

Siemens 440 User Manual

Page 244

background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

244

6SE6400-5BB00-0BP0

P2816[2]

BI: OR 1

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: TECH

Active: first confirm

QuickComm.: No

Max: 4000:0

P2816[0], P2816[1] define inputs of OR 1 element, output is P2817.

A
B

C

P2816

r2817

A

B

C

0

0

0

0

1

1

1

0

1

1

1

1

1

P2800 P2801[3]

Index0

Index1

Index:

P2816[0] : Binector input 0 (BI 0)
P2816[1] : Binector input 1 (BI 1)

Dependency:

P2801[3] is active level for the OR element.

r2817

BO: OR 1

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: TECH

Max: -

Output of OR 1 element. Displays or logic of bits defined in P2816[0], P2816[1].

Dependency:

P2801[3] is active level for the OR element.

P2818[2]

BI: OR 2

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: TECH

Active: first confirm

QuickComm.: No

Max: 4000:0

P2818[0], P2818[1] define inputs of OR 2 element, output is P2819.

Index:

P2818[0] : Binector input 0 (BI 0)
P2818[1] : Binector input 1 (BI 1)

Dependency:

P2801[4] is active level for the OR element.

r2819

BO: OR 2

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: TECH

Max: -

Output of OR 2 element. Displays or logic of bits defined in P2818[0], P2818[1].

Dependency:

P2801[4] is active level for the OR element.

P2820[2]

BI: OR 3

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: TECH

Active: first confirm

QuickComm.: No

Max: 4000:0

P2820[0], P2820[1] define inputs of OR 3 element, output is P2821.

Index:

P2820[0] : Binector input 0 (BI 0)
P2820[1] : Binector input 1 (BI 1)

Dependency:

P2801[5] is active level for the OR element.

r2821

BO: OR 3

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: TECH

Max: -

Output of OR 3 element. Displays or logic of bits defined in P2820[0], P2820[1].

Dependency:

P2801[5] is active level for the OR element.

Level

3

Level

3

Level

3

Level

3

Level

3

Level

3