Siemens 440 User Manual
Page 244
Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
244
6SE6400-5BB00-0BP0
P2816[2]
BI: OR 1
Min: 0:0
CStat:
CUT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: TECH
Active: first confirm
QuickComm.: No
Max: 4000:0
P2816[0], P2816[1] define inputs of OR 1 element, output is P2817.
A
B
C
P2816
r2817
A
B
C
0
0
0
0
1
1
1
0
1
1
1
1
1
P2800 P2801[3]
Index0
Index1
Index:
P2816[0] : Binector input 0 (BI 0)
P2816[1] : Binector input 1 (BI 1)
Dependency:
P2801[3] is active level for the OR element.
r2817
BO: OR 1
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: TECH
Max: -
Output of OR 1 element. Displays or logic of bits defined in P2816[0], P2816[1].
Dependency:
P2801[3] is active level for the OR element.
P2818[2]
BI: OR 2
Min: 0:0
CStat:
CUT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: TECH
Active: first confirm
QuickComm.: No
Max: 4000:0
P2818[0], P2818[1] define inputs of OR 2 element, output is P2819.
Index:
P2818[0] : Binector input 0 (BI 0)
P2818[1] : Binector input 1 (BI 1)
Dependency:
P2801[4] is active level for the OR element.
r2819
BO: OR 2
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: TECH
Max: -
Output of OR 2 element. Displays or logic of bits defined in P2818[0], P2818[1].
Dependency:
P2801[4] is active level for the OR element.
P2820[2]
BI: OR 3
Min: 0:0
CStat:
CUT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: TECH
Active: first confirm
QuickComm.: No
Max: 4000:0
P2820[0], P2820[1] define inputs of OR 3 element, output is P2821.
Index:
P2820[0] : Binector input 0 (BI 0)
P2820[1] : Binector input 1 (BI 1)
Dependency:
P2801[5] is active level for the OR element.
r2821
BO: OR 3
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: TECH
Max: -
Output of OR 3 element. Displays or logic of bits defined in P2820[0], P2820[1].
Dependency:
P2801[5] is active level for the OR element.
Level
3
Level
3
Level
3
Level
3
Level
3
Level
3