Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 90

90
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 3 Protective Trip & Warning Functions
Table 23 - Protective Warning Summary
Function
Factory
Default
Warning Level
Inhibit Time
➊
Range
Default Range
Default
Overload
Disabled
0…100%
➋
85%
Phase Loss
Ground Fault (193/592-EC2)
Disabled
Internal 1…5 A
2.0 A
0…250 s
10 s
Ground Fault (193/592-EC3)
External 0.02…5 A
➌
Stall
Jam
Disabled
50…600%
150%
0…250 s
10 s
Underload
10…100%
➍
70%
Thermistor (PTC)
Current Imbalance
10…100%
20%
0…250 s
10 s
Comm Fault
Comm Idle
Voltage Input Module
Hardware Fault
➎
Enabled
Under Voltage L-L
➎
Disabled
0...65535
400
0…250 s
10 s
Over Voltage L-L
➎
Voltage Unbalance
➎
0…100
85
Phase Rotation
➎
1…2
1
Under Frequency
➎
0…250
58
Over Frequency
➎
62
Under Real Power
➎
0…32767
Over Real Power
➎
Under Consumed kVAR
➎
Over Consumed kVAR
➎
Under Generated kVAR
➎
-32767…0
Over Generated kVAR
➎
Under Power kVA
➎
0…32767
Over Power kVA
➎
Under Power Factor Lagging
➎
-100…0
-95
Over Power Factor Lagging
➎
-90
Under Power Factor Leading
➎
0...100
95
Over Power Factor Leading
➎
90
➊
The inhibit time setting parameters are applicable to both the trip and warning functions.
➋
Overload warning setting is entered as a percentage of the thermal capacity utilized.
➌
Must use Ground Fault Sensors (Catalog Number 193-CBCT_).
➍
50…100% for devices with FRN 1.003 and earlier.
➎
Available on 193/592-EC5 only.