Rockwell Automation Publication 193-UM002I-EN-P - December 2011

Chapter 11 Using DeviceLogix™

9.

Repeat steps 3 through 8 to add a second BOR function block that
monitors Input 3 and 4 to control Output B of the E3 Plus.

10.

Disable Edit mode by de-selecting the Edit mode button

or through

the Tools menu.

11.

If programming the function block offline, exit the Function Block editor
and go online with the DeviceNetwork. Download the parameters,
including the DeviceLogix Function Blocks, to the E3 Plus and proceed to
step 12. If programming the function block online, download the

Function Blocks to the E3 Plus by selecting the Download button

or

through the Communications menu.