Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 143
![background image](/manuals/577428/143/background.png)
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
143
Monitoring Parameters Chapter 6
TRIP LOG 2
This parameter records the trip previous to
Trip Log 1.
Parameter Number
18
Access Rule
Get
Data Type
WORD
Object Mapping
0x29-1-118
Group
Monitor
Units
—
Minimum Value
See Trip Status table
Maximum Value
See Trip Status table
Default Value
None
TRIP LOG 3
This parameter records the trip previous to
Trip Log 2.
Parameter Number
19
Access Rule
Get
Data Type
WORD
Object Mapping
0x29-1-119
Group
Monitor
Units
—
Minimum Value
See Trip Status table
Maximum Value
See Trip Status table
Default Value
None
TRIP LOG 4
This parameter records the trip previous to
Trip Log 3.
Parameter Number
20
Access Rule
Get
Data Type
WORD
Object Mapping
0x29-1-120
Group
Monitor
Units
—
Minimum Value
See Trip Status table
Maximum Value
See Trip Status table
Default Value
None
DEVICE STATUS
This parameter provides status
information of the E3 Overload Relay as
outlined in the table below.
1 = On or Present
0 = Off or Not Present
Parameter Number
21
Access Rule
Get
Data Type
WORD
Object Mapping
0x29-1-121
Group
Monitor
Units
—
Minimum Value
—
Maximum Value
—
Default Value
None
Bit
Function:
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
X
Trip
X
Warning
X
Output A
X
Output B (E3 Plus)
X
Input #1
X
Input #2
X
Input #3 (E3 Plus)
X
Input #4 (E3 Plus)
X
Motor Current
X
Ground Fault Current (E3
Plus)