Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 255
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
255
DeviceNet™ Information Appendix B
The following common services will be implemented for the DPI Fault Object.
The table below lists EC1, EC2, EC3 and EC5 Fault Codes, Fault Text, and Fault
Help Strings.
Table 123 -
Attribute ID
Access
Rule
Name
Data Type
Value
0
Get
Full/All Info
Struct of:
Fault Code
UINT
See Table 124 -
Fault Source
Struct of:
DPI Port Number
USINT
0
Device Object
Instance
USINT
0x2c
Fault Text
BYTE[16]
See Table 124 -
Fault Time Stamp
Struct of:
Timer Value
ULDINT
Timer Descriptor
WORD
Help Object Instance
USINT
Fault Data
1
Get
Basic Info
Struct of:
Fault Code
UINT
See Table 124 -
Fault Source
Struct of:
DPI Port Number
USINT
0
Device Object
Instance
USINT
0x2C
Fault Time Stamp
Struct of:
Timer Value
ULINT
Timer Descriptor
WORD
3
Get
Help Text
STRING
See Table 124 - below
Service
Code
Implemented for:
Service
Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
Yes
No
Set_Attribute_Single
Table 124 - EC1, EC2, EC3 and EC5 Fault Codes, Fault Text, and Fault Help Strings
Fault
Code
Fault Text
Help Text
0
No Fault
No Fault Conditions Detected
1
Test Trip
Test trip caused by holding the Test/Rest button for 2 seconds
2
Overload
Motor current overload condition
3
Phase Loss
Phase current Loss detected in one of the motor phases
4
Ground Fault
Power conductor or motor winding is shorting to ground
5
Stall
Motor has not reached full speed by the end of Stall Enable Time