DeviceNet™ Information Appendix B

The following common services will be implemented for the DPI Fault Object.

The table below lists EC1, EC2, EC3 and EC5 Fault Codes, Fault Text, and Fault
Help Strings.

Table 123 -

Attribute ID

Access
Rule

Name

Data Type

Value

0

Get

Full/All Info

Struct of:

Fault Code

UINT

See Table 124 -

Fault Source

Struct of:

DPI Port Number

USINT

0

Device Object
Instance

USINT

0x2c

Fault Text

BYTE[16]

See Table 124 -

Fault Time Stamp

Struct of:

Timer Value

ULDINT

Timer Descriptor

WORD

Help Object Instance

USINT

Fault Data

1

Get

Basic Info

Struct of:

Fault Code

UINT

See Table 124 -

Fault Source

Struct of:

DPI Port Number

USINT

0

Device Object
Instance

USINT

0x2C

Fault Time Stamp

Struct of:

Timer Value

ULINT

Timer Descriptor

WORD

3

Get

Help Text

STRING

See Table 124 - below

Service
Code

Implemented for:

Service
Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

Yes

No

Set_Attribute_Single

Table 124 - EC1, EC2, EC3 and EC5 Fault Codes, Fault Text, and Fault Help Strings

Fault
Code

Fault Text

Help Text

0

No Fault

No Fault Conditions Detected

1

Test Trip

Test trip caused by holding the Test/Rest button for 2 seconds

2

Overload

Motor current overload condition

3

Phase Loss

Phase current Loss detected in one of the motor phases

4

Ground Fault

Power conductor or motor winding is shorting to ground

5

Stall

Motor has not reached full speed by the end of Stall Enable Time