Logic Controller Communication Examples Chapter 10

Set up the MSG instruction in the Configuration tab to read the list of attributes
(Parameter Groups) by configuring the following fields:

• Message Type:

CIP Generic

• Service Type:

Custom

• Service Code:

0x03 (hex)

• Class: 0x375

(hex)

• Instance: 1

(dec)

• Attribute: 0x00

(hex)

• Source Element:

MSG_Read_Request[0]

• Source Length:

14 (Bytes)

• Destination: MSG_Read_Data

Next, set up the communications path in the Communication tab to read data
from the E3 Plus Overload Relay located at Node 6 by configuring the
communication Path as “DNET, 2, 6”.

DNET

- the name of the 1769-SDN DeviceNet Scanner

2

– The port number of the 1769-SDN DeviceNet Scanner

6

– The node address of the E3 Plus Overload Relay