Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 181
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
181
Power Parameters Chapter 8
OPFLD Trip Delay
This parameter allows the installer to
program a time duration for which an
over power factor leading condition
must exist prior to the device tripping.
Parameter Number
286
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-11E-01
Group
Power Setup
Units
Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0
OPFLD Trip Level
This parameter sets the over power
factor leading trip level.
Parameter Number
287
Access Rule
Get/Set
Data Type
SINT
Object Mapping
0Fhex-11F-01
Group
Power Setup
Units
%
Minimum Value
0
Maximum Value
100
Default Value
95
OPFLD Warn Level
This parameter sets the over power
factor leading warning level.
Parameter Number
288
Access Rule
Get/Set
Data Type
SINT
Object Mapping
0Fhex-120-01
Group
Power Setup
Units
%
Minimum Value
0
Maximum Value
100
Default Value
90
Demand Period
This parameter sets the time period in
minutes for which the demand
calculation averages energy usage.
Parameter Number
291
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-123-01
Group
Power Setup
Units
Minutes
Minimum Value
1
Maximum Value
255
Default Value
15
Num of Periods
This parameter sets the number of
periods to average for the demand
calculation.
Parameter Number
292
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-124-01
Group
Power Setup
Units
—
Minimum Value
1
Maximum Value
15
Default Value
1