Rockwell Automation Publication 193-UM002I-EN-P - December 2011

181

Power Parameters Chapter 8

OPFLD Trip Delay

This parameter allows the installer to
program a time duration for which an
over power factor leading condition
must exist prior to the device tripping.

Parameter Number

286

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-11E-01

Group

Power Setup

Units

Seconds

Minimum Value

0.1

Maximum Value

25.0

Default Value

1.0

OPFLD Trip Level

This parameter sets the over power
factor leading trip level.

Parameter Number

287

Access Rule

Get/Set

Data Type

SINT

Object Mapping

0Fhex-11F-01

Group

Power Setup

Units

%

Minimum Value

0

Maximum Value

100

Default Value

95

OPFLD Warn Level

This parameter sets the over power
factor leading warning level.

Parameter Number

288

Access Rule

Get/Set

Data Type

SINT

Object Mapping

0Fhex-120-01

Group

Power Setup

Units

%

Minimum Value

0

Maximum Value

100

Default Value

90

Demand Period

This parameter sets the time period in
minutes for which the demand
calculation averages energy usage.

Parameter Number

291

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-123-01

Group

Power Setup

Units

Minutes

Minimum Value

1

Maximum Value

255

Default Value

15

Num of Periods

This parameter sets the number of
periods to average for the demand
calculation.

Parameter Number

292

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-124-01

Group

Power Setup

Units

Minimum Value

1

Maximum Value

15

Default Value

1