120

Rockwell Automation Publication 193-UM002I-EN-P - December 2011

Chapter 5 Programmable Parameters

Table 55 - Current Imbalance Parameters Detail

CI INHIBIT TIME

This parameter defines the amount of time

current imbalance detection is inhibited

during a motor starting sequence.

Parameter Number

49

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-149

Group

Advanced Setup

Units

Seconds

Minimum Value

0

Maximum Value

250

Default Value

10

CI TRIP DELAY

This parameter allows the installer to

program a time duration that a current

imbalance condition must exist at the

programmed level prior to the device

tripping.

Parameter Number

50

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-150

Group

Advanced Setup

Units

Seconds

Minimum Value

0.1

Maximum Value

25.0

Default Value

5.0

CI TRIP LEVEL

This parameter sets the current imbalance

trip level.

Parameter Number

51

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-151

Group

Advanced Setup

Units

%

Minimum Value

10

Maximum Value

100

Default Value

35

CI WARN LEVEL

This parameter sets the current imbalance

warning level.

Parameter Number

52

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-152

Group

Advanced Setup

Units

%

Minimum Value

10

Maximum Value

100

Default Value

20