Rockwell Automation Publication 193-UM002I-EN-P - December 2011

Chapter 7 Voltage Parameters

UF Warn Level

This parameter sets the under frequency
warning level.

Parameter Number

236

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-EC-01

Group

Voltage Setup

Units

Hz

Minimum Value

0

Maximum Value

250

Default Value

58

OF Inhibit Time

This parameter defines the amount of time
for which an over frequency detection is
inhibited during a motor starting
sequence.

Parameter Number

237

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-ED-01

Group

Voltage Setup

Units

Seconds

Minimum Value

0

Maximum Value

250

Default Value

10

OF Trip Delay

This parameter allows the installer to
program a time duration for which an over
frequency condition must exist prior to the
device tripping.

Parameter Number

238

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-EE-01

Group

Voltage Setup

Units

Seconds

Minimum Value

0.1

Maximum Value

25.0

Default Value

1.0

OF Trip Level

This parameter sets the over frequency trip
level.

Parameter Number

239

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-EF-01

Group

Voltage Setup

Units

Hz

Minimum Value

0

Maximum Value

250

Default Value

63

OF Warn Level

This parameter sets the over frequency
warning level.

Parameter Number

240

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-F0-01

Group

Voltage Setup

Units

Hz

Minimum Value

0

Maximum Value

62

Default Value

58