Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 156

156
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 7 Voltage Parameters
UF Warn Level
This parameter sets the under frequency
warning level.
Parameter Number
236
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-EC-01
Group
Voltage Setup
Units
Hz
Minimum Value
0
Maximum Value
250
Default Value
58
OF Inhibit Time
This parameter defines the amount of time
for which an over frequency detection is
inhibited during a motor starting
sequence.
Parameter Number
237
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-ED-01
Group
Voltage Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
10
OF Trip Delay
This parameter allows the installer to
program a time duration for which an over
frequency condition must exist prior to the
device tripping.
Parameter Number
238
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-EE-01
Group
Voltage Setup
Units
Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0
OF Trip Level
This parameter sets the over frequency trip
level.
Parameter Number
239
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-EF-01
Group
Voltage Setup
Units
Hz
Minimum Value
0
Maximum Value
250
Default Value
63
OF Warn Level
This parameter sets the over frequency
warning level.
Parameter Number
240
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-F0-01
Group
Voltage Setup
Units
Hz
Minimum Value
0
Maximum Value
62
Default Value
58