Chapter 8 Power Parameters

Figure 1: Explanation of Power Parameter Signs

The following chart illustrates the reported power parameters based on the
chosen voltage mode. Parameters that do not have an "X" will report 0.

IMPORTANT

The E3 Plus model EC5 will report 0 for all power based
parameters if the voltage is below 50V L-L .

IMPORTANT

The E3 Plus model EC5 is capable of reporting power values
when the voltage is greater than 690V L-L and for frequencies
less than 40 Hz or greater than 80 Hz; however, the accuracy of
the value may be compromised.

Table 6: Power Reporting Summary

Parameter Name

Single Phase

Delta

Wye

Open Delta Delta with PT

L1 Real Power (kW)

X

X

L2 Real Power (kW)

X

X

L3 Real Power (kW)

X

Total Real Power (kW)

X

X

X

X

L1 Reactive Power (kVAR)

X

X

L2 Reactive Power (kVAR)

X

X

L3 Reactive Power (kVAR)

X

Total Reactive Power (kVAR)

X

X

X

X

L1 Apparent Power (kVA)

X

X

L2 Apparent Power (kVA)

X

X

L3 Apparent Power (kVA)

X

Total Apparent Power (kVA)

X

X

X

X

X

L1 Power Factor (PF)

X

X

L2 Power Factor (PF)

X

X

L3 Power Factor (PF)

X

Total Power Factor (PF)

X

X

X

X

kWh

X

X

X

kVARh Consumed

X

X

X

X

kVARh Generated

X

X

X

I

IV

II

III

90°

270°

180°

Pf = 0
+kVAR (Consumed)

Pf = 0
-kVAR (Generated)

Pf = 100%
+kW (Consumed)

Pf = 100%
-kW (Generated)

(Power Factor
Lagging)
(-)

(Power Factor
Leading)
(+)

(Power Factor
Lagging)
(-)

(Power Factor
Leading)
(+)