beautypg.com

Control supervisor object – class code 0x29 – Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual

Page 247

background image

Rockwell Automation Publication 193-UM002I-EN-P - December 2011

247

DeviceNet™ Information Appendix B

Control Supervisor Object
– Class Code 0x29

The following instance attributes are supported for the Control Supervisor
Object.

Service
Code

Implemented for:

Service
Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Table 115 - Control Supervisor Object Instance Attributes

Attribute
ID

Access
Rule

Name

Data
Type

Value

10

Get

Tripped

BOOL

0 = No Fault present
1 = Fault Latched

11

Get

Warning

BOOL

0 = No Warning present
1 = Warning present (not latched)

12

Get/Set

Fault Reset

BOOL

0->1 = Trip Reset
otherwise no action

13

Get

Trip Code

UINT

ODVA Trip Code – In trip state
indicates cause of trip; If not tripped,
indicates cause of last trip.

14

Get

Warning Code

UINT

ODVA Warning Code - In warning
state indicates cause of warning; If no
warning, indicates cause of last
warning.

17

Get/Set

Force Trip

BOOL

0->1 = Trip. Test trip generated. This
attribute returns object state conflict
when “Test Enable” bitr is set in Trip
Enable.

100

Get

Elapsed Time

UINT

Logs motor-on (Current Present)
hours.

101

Get

Starts Counter

UINT

Logs the number of motor starts.

102

Get

Starts Available

USINT

Starts left for the programmed start
interval

103

Get

Time To Start

UINT

Time before the next start can be
preformed (in seconds)

104

Get/Set

Starts per Hour

USINT

Number of starts allowed per hour.

105

Get/Set

Starts Interval

UINT

Minimum time between starts,

106

Get/Set

PM – Start Count

UINT

The Preventative Maintenance Start
Count flag is set after this number of
starts

107

Get/Set

PM – Oper Hours

UINT

The Preventative Maintenance
Operating Hours flag is set after this
number of hours

108

Get/Set

Test Enable

BOOL

Enables/Disables the Test Button.

109

Get

Warning Log 0

WORD

Enumerated same as attribute 115

110

Get

Warning Log 1

WORD

Enumerated same as attribute 115

111

Get

Warning Log 2

WORD

Enumerated same as attribute 115

112

Get

Warning Log 3

WORD

Enumerated same as attribute 115

113

Get

Warning Log 4

WORD

Enumerated same as attribute 115