Rockwell Automation Publication 193-UM002I-EN-P - December 2011

Chapter 2 Installation & Wiring

Table 6 - Maximum Wire Length (PTC & input)

Table 7 - Ground Fault Sensor Terminals (S1 & S2)

Flexible-Stranded with Ferrule Metric Single

0.25…2.5 mm

2

Multiple

0.5...0.75 mm

2

0.55 Nm

Coarse-Stranded/Solid Metric

Single

0.2...2.5 mm

2

Multiple

0.2...1.5 mm

2

0.55 Nm

Minimum Cross Section

mm

2

0.5

0.75

1.5

2.5

4.0

AWG

20

18

16

14

12

Maximum Length

meters

160

250

400

600

1000

feet

525

825

1300

1950

3200

The use of shielded cable is recommended for the PTC thermistor circuit to assist in

obtaining compliance with Electromagnetic Compatibility (EMC) requirements.
Shielded cable is recommended for the input circuits, where wire lengths exceed 200
meters (656 feet).

NOTE:

For reliable input signal processing, input wiring should be routed in raceways

separate from power cabling.

Wire Type

Shielded, Twisted Pair

Cross Section

0.2…4.0 mm

2

(#24…12 AWG)

Torque

0.55 N

·

m (5 lb.-in.)

Wire Type

Conductor Torque All Cat. No. Types