Rockwell Automation Publication 193-UM002I-EN-P - December 2011

225

Appendix

A

Specifications

Electrical Specifications

➊ Exception: Any E3 Overload Relay that uses an external ground fault sensor is limited to 50/60 Hz detection.

Figure 13: E3 & E3 Plus Power Supply Current

Figure 3: Motor/Load Ratings

Terminals

1/L1, 3/L2, 5/L3, 2/T1, 4/T2, 6/T3

Rated Insulation Voltage (U

i

)

690V AC

Rated Operating Voltage (U

e

)

IEC:
UL:

690V AC
600V AC

Rated Impulse Voltage (U

imp

)

6 kV

Rated Operating Current (I

e

)

See Catalog Number Explanation

Rated Frequency

20...250 Hz ➊

Short Circuit Ratings

See Chapter 2

Number of Poles

3

Application

Single-phase or Three-phase

Table 16: Power Supply Ratings

Terminals

DeviceNet Connector: V+ (Red), V- (Black)

Rated Supply Voltage (U

s

)

24V DC

Operating Range

11...25V DC

Rated Supply Current

See Chart Below

Maximum Surge Current at Power-Up

3 A

Maximum Power Consumption
E3:
E3 Plus:

3.2 W
4.2 W

Maximum Power Interruption Time
@ 11V DC:
@ 25V DC:

1 ms
10 ms

E3 & E3 Plus Supply Current

0

50

100

150

200

250

300

350

10

15

20

25

30

Input Voltage (V)

Input Current (mA)

E3 Plus
E3