Devicenet setup group – Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 125
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
125
Programmable Parameters Chapter 5
DeviceNet Setup Group
Table 61 - Assembly Parameters Detail
CLEAR QUEUE (Series C and later)
This parameter allows the user to clear the
Trip Logs, Warning Logs, Starts Counter,
and the Elapsed Time. Setting the Clear
Queue parameter to "1" will clear/reset the
Trip Logs, Warning Logs, Starts Counter,
and the Elapsed Time parameters at the
same time.
Parameter Number
104
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
29hex-1-132
Group
Reset/Lock
Units
—
Minimum Value
0 = Ready
Maximum Value
1 = Clear
Default Value
0
OUTPUT ASSEMBLY
This parameter is used to select the desired
output assembly. See Appendix B for a
listing of available assemblies
Parameter Number
59
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0xB4-1-16
Group
DeviceNet Setup
Units
—
Minimum Value
0
Maximum Value
105
Default Value
103 (E3)
105 (E3 Plus)
INPUT ASSEMBLY
This parameter is used to select the desired
input assembly. See Appendix B for a
listing of available assemblies
Parameter Number
60
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0xB4-1-17
Group
DeviceNet Setup
Units
—
Minimum Value
0
Maximum Value
107
Default Value
100
ASSY WORD0 PARAM
This parameter assigns the parameter
value to be placed in Word 0 of Input
Assembly 100.
Parameter Number
61
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0xB4-1-7
Group
DeviceNet Setup
Units
—
Minimum Value
0
Maximum Value
302
➊
Default Value
21
ASSY WORD1 PARAM
This parameter assigns the parameter
value to be placed in Word 1 of Input
Assembly 100.
Parameter Number
62
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0xB4-1-8
Group
DeviceNet Setup
Units
—
Minimum Value
0
Maximum Value
302
➊