Chapter 8 Power Parameters
OVA Trip Level
This parameter sets the over apparent
power (kVA) trip level.
Parameter Number
271
Access Rule
Get/Set
Data Type
INT
Object Mapping
0Fhex-10F-01
Group
Power Setup
Units
kVA
Minimum Value
0
Maximum Value
32767
Default Value
—
OVA Warn Level
This parameter sets the over apparent
power (kVA) warning level.
Parameter Number
272
Access Rule
Get/Set
Data Type
INT
Object Mapping
0Fhex-110-01
Group
Power Setup
Units
kVA
Minimum Value
0
Maximum Value
32767
Default Value
—
UPFLG Inhibit Time
This parameter defines the amount of
time for which an under power factor
lagging detection is inhibited during a
motor starting sequence.
Parameter Number
273
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-111-01
Group
Power Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
10
UPFLG Trip Delay
This parameter allows the installer to
program a time duration for which an
under power factor lagging condition
must exist prior to the device tripping.
Parameter Number
274
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-112-01
Group
Power Setup
Units
Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0
UPFLG Trip Level
This parameter sets the under power
factor lagging trip level.
Parameter Number
275
Access Rule
Get/Set
Data Type
SINT
Object Mapping
0Fhex-113-01
Group
Power Setup
Units
%
Minimum Value
-100
Maximum Value
0
Default Value
-90