Chapter 3 Protective Trip & Warning Functions

Figure 30 - Time-Current Characteristics for Trip Classes 5, 10, 20, & 30

For trip class time-current characteristics other than 5, 10, 20, or 30, scale the
Class 10 trip time according to the following table:

Table 19 - Time-Current Characteristic Scaling Factors

Trip Class

Trip Class
10 Multiplier Trip Class

Trip Class
10 Multiplier Trip Class

Trip Class
10 Multiplier

5

0.5

14

1.4

23

2.3

6

0.6

15

1.5

24

2.4

7

0.7

16

1.6

25

2.5

8

0.8

17

1.7

26

2.6

9

0.9

18

1.8

27

2.7

10

1.0

19

1.9

28

2.8

11

1.1

20

2.0

29

2.9

12

1.2

21

2.1

30

3.0

13

1.3

22

2.2

1

10

100

1000

100%

1000%

Time (seconds)

Trip Class 5

Current (% FLA)

Trip Class 30

1

10

100

1000

10000

100%

1000%

Current (% FLA)

Time (seconds)

1

10

100

1000

10000

100%

1000%

Trip Class 20

Time (seconds)

Current (% FLA)

1

10

100

1000

100%

1000%

Time (seconds)

Trip Class 10

Current (% FLA)

Cold Trip
Hot Trip