Starts Available (Series C and later)

This parameter reports the number of
starts currently available based on the
Start Inhibit settings (parameter 99,
Starts/Hour).

Parameter Number

97

Access Rule

Get

Data Type

USINT

Object Mapping

29hex-1-102

Group

Monitor

Units

-

Minimum Value

0

Maximum Value

120

Default Value

0

Time to Start (Series C and later)

This parameter reports the timed non-zero
value when a Start Inhibit trip is in effect
(parameter 100, Starts Interval).

Parameter Number

98

Access Rule

Get

Data Type

UINT

Object Mapping

29hex-1-103

Group

Monitor

Units

Seconds

Minimum Value

0

Maximum Value

3600

Default Value

0