Trip history and snapshot, Trip and warning history, Tripwarn history group – Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 183: Chapter
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
183
Chapter
9
Trip History and Snapshot
Trip and Warning History
The E3 Plus Overload Relay with firmware revision 5.01 and higher offers the
user programmable Trip History and Warning History diagnostic information.
The user can select the specific trip and warning features that get written to the
five record Trip History and Warning History.
TripWarn History Group
Trip History 0
This parameter reports the latest trip
written to the Trip History. Refer to Table
8.1 for the Trip History record
identification.
Parameter Number
132
Access Rule
Get
Data Type
UINT
Object Mapping
0Fhex-84-01
Group
TripWarn History
Units
—
Minimum Value
0
Maximum Value
48
Default Value
—
Trip History 1
This parameter reports the trip written to
the Trip History previous to Trip History 0.
Refer to Table 8.1 for the Trip History
record identification.
Parameter Number
133
Access Rule
Get
Data Type
UINT
Object Mapping
0Fhex-85-01
Group
TripWarn History
Units
—
Minimum Value
0
Maximum Value
48
Default Value
—
Trip History 2
This parameter reports the trip written to
the Trip History previous to Trip History 1.
Refer to Table 8.1 for the Trip History
record identification.
Parameter Number
134
Access Rule
Get
Data Type
UINT
Object Mapping
0Fhex-86-01
Group
TripWarn History
Units
—
Minimum Value
0
Maximum Value
48
Default Value
—