Communication fault protection, Comm fault trip – Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual

Page 64

background image

64

Rockwell Automation Publication 193-UM002I-EN-P - December 2011

Chapter 3 Protective Trip & Warning Functions

• TRIP/WARN LED will flash an amber 9-blink pattern,
• bit 8 in Warning Status, Parameter 15, will set to “1”, and
• bit 1 in Device Status, Parameter 21, will set to “1”.

CI Warn Level, Parameter 52, allows the installer to define the percent current
imbalance at which the E3 Overload Relay will indicate a warning. It is user-
adjustable from 10…100%.

Communication Fault

Protection

A disruption of the communication link between the E3 Overload Relay and a
DeviceNet network can result in the loss of application control and/or critical
process diagnostic data. Rapid communication fault detection helps minimize
potential damage due to uncontrolled or unmonitored applications.

Comm Fault Trip

The E3 Overload Relay will trip with a Comm Fault indication if:

• no trip currently exists,
• Comm Fault protection is enabled, and
• the E3 Overload Relay experiences a loss of communication.

If the relay trips on a Comm Fault, the:

• Network Status LED will blink red or become solid red
• TRIP/WARN LED will flash a red 10-blink pattern
• bit 9 in Trip Status, Parameter 14, will set to “1”
• bit 0 in Device Status, Parameter 21, will set to “1”
• Trip Relay contacts will open, and
• outputs will be placed in their Protection Fault State (if so programmed).

IMPORTANT The Current Imbalance Warning function does not include a time delay

feature. Once the CI Inhibit Time has expired, The CI warning indication is
instantaneous.

IMPORTANT The Protection Fault State of OUT A and OUT B is defined by:

OUTA Pr FltState, Parameter 65

OUTA Pr FltValue, Parameter 66

OUTB Pr FltState, Parameter 71

OUTB Pr FltValue, Parameter 72