Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 175

Rockwell Automation Publication 193-UM002I-EN-P - December 2011
175
Power Parameters Chapter 8
OVARC Warn Level
This parameter sets the over reactive
power (kVAR) consumed warning level.
Parameter Number
256
Access Rule
Get/Set
Data Type
INT
Object Mapping
0Fhex-100-01
Group
Power Setup
Units
kVAR
Minimum Value
0
Maximum Value
32767
Default Value
—
UVARG Inhibit Time
This parameter defines the amount of
time for which an under reactive power
(kVAR) generated detection is inhibited
during a motor starting sequence.
Parameter Number
257
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-101-01
Group
Power Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
10
UVARG Trip Delay
This parameter allows the installer to
program a time duration for which an
under reactive power (kVAR) generated
condition must exist prior to the device
tripping.
Parameter Number
258
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-102-01
Group
Power Setup
Units
Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0
UVARG Trip Level
This parameter sets the under reactive
power (kVAR) generated trip level.
Parameter Number
259
Access Rule
Get/Set
Data Type
INT
Object Mapping
0Fhex-103-01
Group
Power Setup
Units
kVAR
Minimum Value
-32768
Maximum Value
0
Default Value
—
UVARG Warn Level
This parameter sets the under reactive
power (kVAR) generated warning level.
Parameter Number
260
Access Rule
Get/Set
Data Type
INT
Object Mapping
0Fhex-104-01
Group
Power Setup
Units
kVAR
Minimum Value
-32768
Maximum Value
0
Default Value
—