UVA Trip Delay

This parameter allows the installer to
program a time duration for which an
under apparent power (kVA) condition
must exist prior to the device tripping.

Parameter Number

266

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-10A-01

Group

Power Setup

Units

Seconds

Minimum Value

0.1

Maximum Value

25.0

Default Value

1.0

UVA Trip Level

This parameter sets the under apparent
power (kVA) trip level.

Parameter Number

267

Access Rule

Get/Set

Data Type

INT

Object Mapping

0Fhex-10B-01

Group

Power Setup

Units

kVA

Minimum Value

0

Maximum Value

32767

Default Value

UVA Warn Level

This parameter sets the under apparent
power (kVA) warning level.

Parameter Number

268

Access Rule

Get/Set

Data Type

INT

Object Mapping

0Fhex-10C-01

Group

Power Setup

Units

kVA

Minimum Value

0

Maximum Value

32767

Default Value

OVA Inhibit Time

This parameter defines the amount of
time for which an over apparent power
(kVA) detection is inhibited during a
motor starting sequence.

Parameter Number

269

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-10D-01

Group

Power Setup

Units

Seconds

Minimum Value

0

Maximum Value

250

Default Value

10

OVA Trip Delay

This parameter allows the installer to
program a time duration for which an
over apparent power (kVA) condition
must exist prior to the device tripping.

Parameter Number

270

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-10E-01

Group

Power Setup

Units

Seconds

Minimum Value

0.1

Maximum Value

25.0

Default Value

1.0