Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 177

Rockwell Automation Publication 193-UM002I-EN-P - December 2011
177
Power Parameters Chapter 8
UVA Trip Delay
This parameter allows the installer to
program a time duration for which an
under apparent power (kVA) condition
must exist prior to the device tripping.
Parameter Number
266
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-10A-01
Group
Power Setup
Units
Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0
UVA Trip Level
This parameter sets the under apparent
power (kVA) trip level.
Parameter Number
267
Access Rule
Get/Set
Data Type
INT
Object Mapping
0Fhex-10B-01
Group
Power Setup
Units
kVA
Minimum Value
0
Maximum Value
32767
Default Value
—
UVA Warn Level
This parameter sets the under apparent
power (kVA) warning level.
Parameter Number
268
Access Rule
Get/Set
Data Type
INT
Object Mapping
0Fhex-10C-01
Group
Power Setup
Units
kVA
Minimum Value
0
Maximum Value
32767
Default Value
—
OVA Inhibit Time
This parameter defines the amount of
time for which an over apparent power
(kVA) detection is inhibited during a
motor starting sequence.
Parameter Number
269
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-10D-01
Group
Power Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
10
OVA Trip Delay
This parameter allows the installer to
program a time duration for which an
over apparent power (kVA) condition
must exist prior to the device tripping.
Parameter Number
270
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-10E-01
Group
Power Setup
Units
Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0