Chapter 5 Programmable Parameters

Advanced Setup Group

Table 43 - The parameters contained in the Advanced Setup Group are also
contained within the Overload Setup Group. Refer to Overload Setup Group on
page 111 f
or more detail on these parameters.

Table 44 - Trip Enable Parameter Detail

Table 45 - Trip Enable Bit Function Detail

Table 46 - Warning Enable Parameter Detail

TRIP ENABLE

This parameter allows the installer to

enable or disable trip functions separately.

Overload, Phase Loss, and Comm Fault are

enabled from the factory.

1 = Enabled
0 = Disabled

Parameter Number

24

Access Rule

Get/Set

Data Type

WORD

Object Mapping

0x29-1-124

Group

Advanced Setup

Units

Minimum Value

0000000000000000

Maximum Value

1111111111111111

Default Value

0000001000000110

Bit

Function

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

X

Overload

X

Phase Loss

X

Ground Fault (E3 Plus)

X

Stall

X

Jam

X

Underload

X

PTC (E3 Plus)

X

Current Imbalance

X

Comm Fault

X

Comm Idle


X

Remote Trip

X

Start Inhibit — Series C & Later

WARNING ENABLE

This parameter allows the installer to

enable or disable warning functions

separately. All warning functions are

disabled from the factory.

1 = Enabled
0 = Disabled

Parameter Number

25

Access Rule

Get/Set

Data Type

WORD

Object Mapping

0x29-1-125

Group

Advanced Setup

Units

Minimum Value

0000000000000000

Maximum Value

1111111111111111

Default Value

0000000000000000