Chapter 5 Programmable Parameters
Advanced Setup Group
Table 43 - The parameters contained in the Advanced Setup Group are also
contained within the Overload Setup Group. Refer to Overload Setup Group on
page 111 for more detail on these parameters.
Table 44 - Trip Enable Parameter Detail
Table 45 - Trip Enable Bit Function Detail
Table 46 - Warning Enable Parameter Detail
TRIP ENABLE
This parameter allows the installer to
enable or disable trip functions separately.
Overload, Phase Loss, and Comm Fault are
enabled from the factory.
1 = Enabled
0 = Disabled
Parameter Number
24
Access Rule
Get/Set
Data Type
WORD
Object Mapping
0x29-1-124
Group
Advanced Setup
Units
—
Minimum Value
0000000000000000
Maximum Value
1111111111111111
Default Value
0000001000000110
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
—
X
Overload
X
Phase Loss
X
Ground Fault (E3 Plus)
X
Stall
X
Jam
X
Underload
X
PTC (E3 Plus)
X
Current Imbalance
X
Comm Fault
X
Comm Idle
—
—
—
X
Remote Trip
X
Start Inhibit — Series C & Later
WARNING ENABLE
This parameter allows the installer to
enable or disable warning functions
separately. All warning functions are
disabled from the factory.
1 = Enabled
0 = Disabled
Parameter Number
25
Access Rule
Get/Set
Data Type
WORD
Object Mapping
0x29-1-125
Group
Advanced Setup
Units
—
Minimum Value
0000000000000000
Maximum Value
1111111111111111
Default Value
0000000000000000