Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 119
![background image](/manuals/577428/119/background.png)
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
119
Programmable Parameters Chapter 5
Table 54 - Underload Parameters Detail
JAM WARN LEVEL
This parameter sets the jam warning level.
Parameter Number
44
Access Rule
Get/Set
Data Type
UINT
Object Mapping
2C
hex
-1-144
Group
Advanced Setup
Units
% FLA
Minimum Value
50
Maximum Value
600
Default Value
150
UL INHIBIT TIME
This parameter defines the amount of time
for which underload detection is inhibited
during a motor starting sequence.
Parameter Number
45
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-145
Group
Advanced Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
10
UL TRIP DELAY
This parameter allows the installer to
program a time duration that an underload
condition must exist at the programmed
level prior to the device tripping.
Parameter Number
46
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-146
Group
Advanced Setup
Units
Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
5.0
UL TRIP LEVEL
This parameter sets the underload trip
level.
Parameter Number
47
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-147
Group
Advanced Setup
Units
% FLA
Minimum Value
10
➊
Maximum Value
100
Default Value
50
UL WARN LEVEL
This parameter sets the underload warning
level.
Parameter Number
48
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-148
Group
Advanced Setup
Units
% FLA
Minimum Value
10
➊
Maximum Value
100
Default Value
70
➊
50…100% for devices with FRN 1.003 and earlier