Rockwell Automation Publication 193-UM002I-EN-P - December 2011

119

Programmable Parameters Chapter 5

Table 54 - Underload Parameters Detail

JAM WARN LEVEL

This parameter sets the jam warning level.

Parameter Number

44

Access Rule

Get/Set

Data Type

UINT

Object Mapping

2C

hex

-1-144

Group

Advanced Setup

Units

% FLA

Minimum Value

50

Maximum Value

600

Default Value

150

UL INHIBIT TIME

This parameter defines the amount of time

for which underload detection is inhibited

during a motor starting sequence.

Parameter Number

45

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-145

Group

Advanced Setup

Units

Seconds

Minimum Value

0

Maximum Value

250

Default Value

10

UL TRIP DELAY

This parameter allows the installer to

program a time duration that an underload

condition must exist at the programmed

level prior to the device tripping.

Parameter Number

46

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-146

Group

Advanced Setup

Units

Seconds

Minimum Value

0.1

Maximum Value

25.0

Default Value

5.0

UL TRIP LEVEL

This parameter sets the underload trip

level.

Parameter Number

47

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-147

Group

Advanced Setup

Units

% FLA

Minimum Value

10

Maximum Value

100

Default Value

50

UL WARN LEVEL

This parameter sets the underload warning

level.

Parameter Number

48

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-148

Group

Advanced Setup

Units

% FLA

Minimum Value

10

Maximum Value

100

Default Value

70

50…100% for devices with FRN 1.003 and earlier