Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 258
258
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Appendix B DeviceNet™ Information
The following common services will be implemented for the DPI Fault Object.
The table below lists EC1, EC2, EC3, EC5 Warning Codes, Warning Text, and
Warning Help Strings.
1
Get
Basic Info
Struct of:
Fault Code
UINT
See Table 127 -
Fault Source
Struct of:
DPI Port Number
USINT
0
Device Object
Instance
USINT
0x2C
Fault Time Stamp
Struct of:
Timer Value
ULINT
Timer Descriptor
WORD
3
Get
Help Text
STRING
See Table 127 -
Service
Code
Implemented for:
Service
Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
Yes
No
Set_Attribute_Single
Table 127 - EC1, EC2, EC3, EC5 Warning Codes, Warning Text, and Warning Help
Strings
Fault
Code
Fault Text
Help Text
0
No Warning
No Warning Conditions Detected
1
Warning 1
2
Overload
Approaching a motor current overload condition
3
Warning 3
4
Ground Fault
Power conductor or motor winding is shorting to ground
5
Warning 5
6
Jam
Motor current has exceed the programmed jam warning level
7
Underload
Motor current has fallen below normal operating levels
8
PTC
PTC input indicates that the motor stator windings
overheated
9
Current Imbal
Phase to phase current imbalance detected
10
Comm Fault
DeviceNet communication loss detected
11
Comm Idle
DeviceNet idle condition detected
12
Warning 12
13
Config Fault
Device parameter configuration problem
14
PM Starts
Number of Starts Warning Level Exceeded
15
PM Oper Hours
Operating Hours Warning Level Exceeded
16
Warning 16
Table 126 - DPI Warning Object Instances
Attribute ID
Access
Rule
Name
Data Type
Value