Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 122

122
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 5 Programmable Parameters
Table 57 - Two-Speed Motor Parameters Detail — E3 Plus
Table 58 - Preventative Maintenance Parameters Detail
2-SPD NET ENABLE
This parameter allows the use of Output
Assemblies 104 and 105 for two-speed
applications.
Parameter Number
87
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
2C
hex
-1-154
Group
Advanced Setup
Units
—
Minimum Value
0 = Disabled
Maximum Value
1 = Enabled
Default Value
0
2-SPEED FLA SET
This parameter allows the user to program
the high speed FLA value of a two-speed
motor.
Parameter Number
88
Access Rule
Get/Set
Data Type
UINT
Object Mapping
2C
hex
-1-155
2C
hex
-1-156
2C
hex
-1-157
Group
Advanced Setup
Units
Amps
Minimum Value
See
Maximum Value
See
Default Value
See
PM - # Starts (Series C and later)
This parameter allows the installer to set a
number of starts after which preventative
maintenance should be performed.
Parameter Number
101
Access Rule
Get/Set
Data Type
UINT
Object Mapping
29hex-1-106
Group
Advanced Setup
Units
—
Minimum Value
0
Maximum Value
65535
Default Value
0
PM - Oper. Hours (Series C and later)
This parameter allows the installer to set
the hours of operation after which
preventative maintenance should be
performed.
Parameter Number
102
Access Rule
Get/Set
Data Type
UINT
Object Mapping
29hex-1-107
Group
Advanced Setup
Units
Hours
Minimum Value
0
Maximum Value
65535
Default Value
0