Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 180
180
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Chapter 8 Power Parameters
UPFLD Inhibit Time
This parameter defines the amount of
time for which an under power factor
leading detection is inhibited during a
motor starting sequence.
Parameter Number
281
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-119-01
Group
Power Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
10
UPFLD Trip Delay
This parameter allows the installer to
program a time duration for which an
under power factor leading condition
must exist prior to the device tripping.
Parameter Number
282
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-11A-01
Group
Power Setup
Units
Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0
UPFLD Trip Level
This parameter sets the under power
factor leading trip level.
Parameter Number
283
Access Rule
Get/Set
Data Type
SINT
Object Mapping
0Fhex-11B-01
Group
Power Setup
Units
%
Minimum Value
0
Maximum Value
100
Default Value
90
UPFLD Warn Level
This parameter sets the under power
factor leading warning level.
Parameter Number
284
Access Rule
Get/Set
Data Type
SINT
Object Mapping
0Fhex-11C-01
Group
Power Setup
Units
%
Minimum Value
0
Maximum Value
100
Default Value
95
OPFLD Inhibit Time
This parameter defines the amount of
time for which an over power factor
leading detection is inhibited during a
motor starting sequence.
Parameter Number
285
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-11D-01
Group
Power Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
10