Chapter 8 Power Parameters

UPFLD Inhibit Time

This parameter defines the amount of
time for which an under power factor
leading detection is inhibited during a
motor starting sequence.

Parameter Number

281

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-119-01

Group

Power Setup

Units

Seconds

Minimum Value

0

Maximum Value

250

Default Value

10

UPFLD Trip Delay

This parameter allows the installer to
program a time duration for which an
under power factor leading condition
must exist prior to the device tripping.

Parameter Number

282

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-11A-01

Group

Power Setup

Units

Seconds

Minimum Value

0.1

Maximum Value

25.0

Default Value

1.0

UPFLD Trip Level

This parameter sets the under power
factor leading trip level.

Parameter Number

283

Access Rule

Get/Set

Data Type

SINT

Object Mapping

0Fhex-11B-01

Group

Power Setup

Units

%

Minimum Value

0

Maximum Value

100

Default Value

90

UPFLD Warn Level

This parameter sets the under power
factor leading warning level.

Parameter Number

284

Access Rule

Get/Set

Data Type

SINT

Object Mapping

0Fhex-11C-01

Group

Power Setup

Units

%

Minimum Value

0

Maximum Value

100

Default Value

95

OPFLD Inhibit Time

This parameter defines the amount of
time for which an over power factor
leading detection is inhibited during a
motor starting sequence.

Parameter Number

285

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-11D-01

Group

Power Setup

Units

Seconds

Minimum Value

0

Maximum Value

250

Default Value

10