Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 248
![background image](/manuals/577428/248/background.png)
248
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
Appendix B DeviceNet™ Information
114
Get
Trip Status
WORD
Bit 0 = Test Trip
Bit 1 = Overload
Bit 2 = Phase Loss
Bit 3 = Ground Fault ➊
Bit 4 = Stall
Bit 5 = Jam
Bit 6 = Underload
Bit 7 = PTC ➊
Bit 8 = Current Imbal
Bit 9 = Comm Fault
Bit 10 = Comm Idle
Bit 11 = NonVol Mem
Bit 12 = Hardware Fault
Bit 13 = Reserved
Bit 14 = Remote Trip
Bit 15 = Blocked Start
115
Get
Warning Status
WORD
Bit 0 = Reserved
Bit 1 = Overload
Bit 2 = Phase Loss
Bit 3 = Ground Fault ➊
Bit 4 = Reserved
Bit 5 = Jam
Bit 6 = Underload
Bit 7 = PTC **
Bit 8 = Current Imbal
Bit 9 = Comm Fault
Bit 10 = Comm Idle
Bit 11 = Reserved
Bit 12 = Config Fault
Bit 13 = PM Starts
Bit 14 = PM Oper Hours
116
Get
Trip Log 0
WORD
Last trip condition. Bit definitions of
the value are the same as attribute
114
117
Get
Trip Log 1
WORD
Last trip condition. Bit definitions of
the value are the same as attribute
114
118
Get
Trip Log 2
WORD
Last trip condition. Bit definitions of
the value are the same as attribute
114
119
Get
Trip Log 3
WORD
Last trip condition. Bit definitions of
the value are the same as attribute
114
120
Get
Trip Log 4
WORD
Last trip condition. Bit definitions of
the value are the same as attribute
114
121
Get
Device Status
WORD
Bit 0 = Trip
Bit 1 = Warning
Bit 2 = OutputA
Bit 3 = OutputB ➊
Bit 4 = Input 1
Bit 5 = Input 2
Bit 6 = Input 3 ➊
Bit 7 = Input 4 ➊
Bit 8 = Motor Current
Bit 9 = GF Current ➊
Bit 10 = Input 5
Bit 11 = Input 6
Bit 12 = Motor Voltage
Table 115 - Control Supervisor Object Instance Attributes
Attribute
ID
Access
Rule
Name
Data
Type
Value