Appendix B DeviceNet™ Information

114

Get

Trip Status

WORD

Bit 0 = Test Trip
Bit 1 = Overload
Bit 2 = Phase Loss
Bit 3 = Ground Fault ➊
Bit 4 = Stall
Bit 5 = Jam
Bit 6 = Underload
Bit 7 = PTC ➊
Bit 8 = Current Imbal
Bit 9 = Comm Fault
Bit 10 = Comm Idle
Bit 11 = NonVol Mem
Bit 12 = Hardware Fault
Bit 13 = Reserved
Bit 14 = Remote Trip
Bit 15 = Blocked Start

115

Get

Warning Status

WORD

Bit 0 = Reserved
Bit 1 = Overload
Bit 2 = Phase Loss
Bit 3 = Ground Fault ➊
Bit 4 = Reserved
Bit 5 = Jam
Bit 6 = Underload
Bit 7 = PTC **
Bit 8 = Current Imbal
Bit 9 = Comm Fault
Bit 10 = Comm Idle
Bit 11 = Reserved
Bit 12 = Config Fault
Bit 13 = PM Starts
Bit 14 = PM Oper Hours

116

Get

Trip Log 0

WORD

Last trip condition. Bit definitions of
the value are the same as attribute
114

117

Get

Trip Log 1

WORD

Last trip condition. Bit definitions of
the value are the same as attribute
114

118

Get

Trip Log 2

WORD

Last trip condition. Bit definitions of
the value are the same as attribute
114

119

Get

Trip Log 3

WORD

Last trip condition. Bit definitions of
the value are the same as attribute
114

120

Get

Trip Log 4

WORD

Last trip condition. Bit definitions of
the value are the same as attribute
114

121

Get

Device Status

WORD

Bit 0 = Trip
Bit 1 = Warning
Bit 2 = OutputA
Bit 3 = OutputB ➊
Bit 4 = Input 1
Bit 5 = Input 2
Bit 6 = Input 3 ➊
Bit 7 = Input 4 ➊
Bit 8 = Motor Current
Bit 9 = GF Current ➊
Bit 10 = Input 5
Bit 11 = Input 6
Bit 12 = Motor Voltage

Table 115 - Control Supervisor Object Instance Attributes

Attribute
ID

Access
Rule

Name

Data
Type

Value