Chapter 12 Troubleshooting

Table 12: Trip/Warn LED Troubleshooting Procedures, Continued

E3 Plus Model EC5 Only

Trip Description

Possible Cause

Corrective Action

Under Real Power
(kW)

1. Real power has exceeded the programmed under real power

level.

2. Improper parameter settings.
3. Relay is applied to the output of a variable frequency drive.

1. Check power system

2. Verify that current is flowing from the line side (L Terminals) to the

load side (L Terminals or contactor mounting stabs) of the relay.

3. Inspect contactor or circuit breaker for proper operation.
4.

Verify that Parameter 243, UW Trip Level, is set properly for the

application.

5. The E3 Plus model EC5 is not intended to be used on the output of a

variable frequency drive.

6. Check to ensure that Parameters 289 and 290, PT Primary and PT

Secondary , are set properly if applicable.

Over Real Power
(kW)

1. Real power has exceeded the programmed over real power

level.

2. Improper parameter settings.
3. Relay is applied to the output of a variable frequency drive.

1. Check power system
2. Verify that current is flowing from the line side (L Terminals or

contactor mounting stabs) to the load side (T terminals) of the relay.

3. Inspect contactor or circuit breaker for proper operation.
4. Verify that Parameter 247, OW Trip Level, is set properly for the

application.

5. The E3 Plus model EC5 is not intended to be used on the output of a

variable frequency drive.

6. Check to ensure that Parameters 289 and 290, PT Primary and PT

Secondary , are set properly if applicable.

Under Reactive
Power Consumed
(+kVAR)

1. Reactive power has exceeded the programmed under reactive

power consumed level.

2. Improper parameter settings.
3. Relay is applied to the output of a variable frequency drive.

1. Check power system
2. Verify that current is flowing from the line side (L Terminals or

contactor mounting stabs) to the load side (T terminals) of the relay.

3. Inspect contactor or circuit breaker for proper operation.
4. Verify that Parameter 251, UVARC Trip Level, is set properly for the

application.

5. The E3 Plus model EC5 is not intended to be used on the output of a

variable frequency drive.

6. Check to ensure that Parameters 289 and 290, PT Primary and PT

Secondary , are set properly if applicable.

Over Reactive
Power Consumed
(+kVAR)

1. Reactive power has exceeded the programmed over reactive

power consumed level.

2. Improper parameter settings.
3. Relay is applied to the output of a variable frequency drive.

1. Check power system
2. Verify that current is flowing from the line side (L Terminals or

contactor mounting stabs) to the load side (T terminals) of the relay.

3. Inspect contactor or circuit breaker for proper operation.
4. Verify that Parameter 255, OVARC Trip Level, is set properly for the

application.

5. The E3 Plus model EC5 is not intended to be used on the output of a

variable frequency drive.

6. Check to ensure that Parameters 289 and 290, PT Primary and PT

Secondary , are set properly if applicable.

Under Reactive
Power Generated
(-kVAR)

1. Reactive power has exceeded the programmed under

reactive power generated level.

2. Improper parameter settings.
3. Relay is applied to the output of a variable frequency drive.

1. Check power system
2. Verify that current is flowing from the line side (L Terminals or

contactor mounting stabs) to the load side (T terminals) of the relay.

3. Inspect contactor or circuit breaker for proper operation.
4. Verify that Parameter 259, UVARG Trip Level, is set properly for the

application.

5. The E3 Plus model EC5 is not intended to be used on the output of a

variable frequency drive.

6. Check to ensure that Parameters 289 and 290, PT Primary and PT

Secondary , are set properly if applicable.